CTRLMax Manual

25
CHAPTER 5
CHAPTER 5 - BOILER SETTINGS
Boiler Settings
Boiler Settings
Model Prstige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 45°C
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Flexible Pump Cong
Flex. Relay 1 (CH)
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Flex. Relay 1 (CH)
CH1 On
CH2
DHW O
MIX OPEN O
MIX CLOSE O
ERROR O
FLAME O
Flex. Relay 1 (CH)
DHW O
MIX OPEN O
MIX CLOSE O
ERROR O
FLAME O
Save & Exit
Each relay function has several options. Activation will hap-
pen when one of the following options has been chosen:
CH1, CH2, DHW, MIX OPEN, MIX CLOSE, ERROR, FLAME.
More than one action can be chosen for one relay (one relay can
become active for CH1 , CH2 and DHW demand when needed.)
Scroll through the settings using the UP or DOWN keys, then
with the OK key, toggle between the On/O status of each
relay. Then go to the next line, until you reach the last line.
When selecting CH 1, the relay is activated at CH 1 demand.
When selecting CH 2, the relay is activated at CH 2 demand.
When selecting DHW, the relay is activated at DHW demand.
When selecting Mix Open, the Mixing valve open input
is activated. Provided there is a mixing valve in the hy-
draulic circuit, runtime is assumed to be 120 sec.
When selecting Mix Close, the Mixing valve close input
is activated. Provided there is a mixing valve in the hy-
draulic circuit, runtime is assumed to be 120 sec.
When selecting ERROR, the relay is activated on error.
When selecting FLAME, the relay is activated when ap-
pliance is running and a ame signal has been detected.
Activate Save & Exit with the OK key. This will ensure that
changed data are stored in the appliance.
Using the RIGHT key then the OK key takes you
back to the previous screen, but THE CHANGED VAL
UES ARE NOT STORED in the memory (Quick escape
route).
To save your changes, make sure to scroll down to the
last line of the screen until Save & Exit is highlighted.
Then activate the function with the OK key.
NOTICE