CTRLMax Manual
24
CHAPTER 5
CHAPTER 5 - BOILER SETTINGS
Boiler Settings
Boiler Settings
Model Prstige Solo
Lockout Temp. 210°F [99°C]
Modbus Address 0=BCST
Pump settings
Ignition Level 3500rpm
Mix zone high limit 45°C
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Pump Settings
Current Pump Cong Modied
Preset Pump Cong
Flexible Pump Cong
Pump PWM minimum 40%
Flexible Pump Cong
Flex. Relay 1 (CH)
Flex. Relay 2 (DHW)
Flex. Relay 3 (P3)
Flex. Relay 4 (ERR)
Flex. Relay 5 (Flame)
Flex. Relay 6 (P4)
Preset Pump Cong
Cong 1
Cong 2
Cong 3
Cong 4
Cong 5
Cong 6
The Pump Settings menu allows to choose the right pump
conguration to the chosen hydraulic conguration.
The Current Pump Cong indicates which conguration is
currently selected for the appliance.
Two appliance conguration modes are available : a preset
conguration mode and a exible conguration mode.
Scroll through the settings using the UP or DOWN keys,
then validate the selection with the OK key.
In the Preset Pump Cong. (preferred selection) you can
choose from a number of preset pump congurations.
Only the congurations usable with a certain model/type
of appliance will appear in the list. Each conguration is
detailed through one or several hydraulic diagrams, a table
indicating the electrical connections and a list of the pa-
rameters to be dened in CTRLMax.
Scroll through the settings using the UP or DOWN keys,
then validate the selection with the OK key.
Although the menu is available in the
INSTINCT units, do not use the Preset Pump
Config Function, unless specified in Fig. 3 on
page 29 thru Fig. 16 on page 42 .
NOTICE
The Flexible Pump Cong. menu allows to customize the
pump conguration to the chosen hydraulic conguration.
Only select this option when the preset congurations do
not oer you a solution. In this menu you have to choose
per relay for which heat demand / function it will be activat-
ed. The relays are allocated as follows by default (see picture
below for physical location on the optional terminal blocks) :
Flex. Relay 1 ..............CH
Flex. Relay 2 ..............DHW
Flex. Relay 3 ..............P3
Flex. Relay 4 ..............ERR
Flex. Relay 5 ..............FL
Flex. Relay 6 ..............P4
Scroll through the settings using the UP or DOWN keys,
then validate the selection with the OK key.
• The use of the Flexible Pump Config. menu is not
possible for the Solo/Excellence (3 way valve).
• Flex Relays 3, 4 and 6 are not available in INSTINCT
units.
NOTICE