CTRLMax Manual
5
CHAPTER 2
CHAPTER 2 - CH SETTINGS
CH Settings
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Heating Operation
Disabled
Enabled
Heating Settings
Heating Operation Enabled
Demand Thermostat & Outd. Curve
CH maximum capacity 100%
CH minimum capacity 0%
Abs. Max. CH Setpoint 186°F
CH1 Max. Setpoint 180°F
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Navigate on the screen using the UP, DOWN, LEFT and RIGHT keys, then
the validate a selection with the OK key. To increase/decrease values, use
the UP and DOWN or LEFT and RIGHT keys, according to the situation and
validate with OK.
NOTICE
CH & DHW Settings
Installer Code
Heating Operation allows the central heating function to be
enabled and disabled.
Select Enabled or Disabled using the UP or DOWN keys, then
store the setting with the OK key.
Enabled - The Appliance will respond to a central heating call.
Disabled - The Appliance will not respond to a central heating call.
The heating operation disabled icon ( ) is displayed
on the home screen when central heating operation
has been disabled.
When heating is disabled the frost protection will
still be active.
Default: Enabled
NOTICE
Demand Type allows the installer to select how a CH Demand
is generated.
Select the CH Demand Type using the UP or DOWN keys, then
store the setting with the OK key.
Default: Thermostat and Outd. Curve
See detail of menu on next page.
CTRLMax_w Instinct_UK version_222171_A01.indd 5 18/07/2019 18:38