Install Instructions
Vent/Air System Installation
6
6. Seal the two components together by placing a
clamp over the connection and pressing down
on the clamp lever. The clamp should be cen-
tered over the connection and the edge of the
clamp should cover the beads on the end of each
component. If the clamp does not cover and
lock onto the component jacket beads, ensure
the components are fully pressed together and
interlocked.
It is very important that the clamp be prop-
erly installed. Failure to properly connect
the vent components could lead to vent fail-
ure and can result in death, serious injury or
substantial property damage.
WARNING
Termination Installation - Horizontal
1. Determine the termination location using the
guidelines listed on page 4 and 5 and drill or cut
a 5 inch hole [12.7 cm].
2. Install the interior support plate on the inside
wall using the screws provided in the kit.
3. Mount the termination fitting through the interi-
or support plate from the exterior side of the
wall. Ensure the air inlet holes of the termina-
tion fitting are facing down and that the fitting
is mounted level.
To determine the appropriate length of the
termination fitting, mount the exterior sup-
port plate temporarily prior to the installation
of the interior support plate. Insert the termi-
nation fitting from the interior side of the wall
through the exterior support plate. The termi-
nation fitting has a formed bead that limits the
distance of penetration through the exterior
support plate. The termination fitting should
be measured and cut to length prior to mount-
ing the support plates. The termination may
be installed through a wall thickness of up to
20” [50.8 cm] maximum. For information on
measuring and cutting the termination fitting,
reference page 7.
4. Mount the exterior support plate around the ter-
mination on the outside wall. Ensure the support
plate is flush to the formed end of the termina-
tion fitting and the fitting is mounted level.
The termination fitting must be installed
level without pitch either to the appliance or
away from appliance.
5. The gaps between the outer pipe of the termina-
tion fitting and the support plates must be sealed
with a high quality silicone caulk. Also apply
the silicone caulk along the outer edge of the
support plates sealing the plates to the wall.
NOTICE
NOTICE
Clamp
Female
End
Male End
Outer Jacket
Bead
Lever
Fig. 6: Vent Joint Assembly
Note: Secure outer sections together where they
overlap with 2 self-drilling screws provided, 90º
apart using low torque setting of driver.