Installation Guide

(Continued from page 1)
IMPORTANT SAFETY INSTRUCTIONS
Recommended to use LED-compatible Wall Dimmers with LED Power
Supplies. Tresco
®
Dimming LED Power Supplies are compatible with
forward phase, reverse phase, triac, MLV and ELV dimmers. For best
operation, use a Dimmer that can be programmed or has an adjustable
low-end dial such as the Lutron
®
C•L and Leviton IllumaTech
®
Universal
Dimmers. If you are unsure of dimmer compatibility, call
1-800-227-1171.
Only install the Wall Dimmer on the input (line voltage) side of the
Power Supply.
Do not add a plug-in to input wires and attempt to dim a receptacle.
This can cause unwanted lighting effects (such as flickering), is
dangerous, and against NEC in certain applications.
Fixture does not illuminate Check installation instructions and diagrams for all
components. Check if the system is wired correctly and
polarities are correct.
Verify that a compatible constant voltage dimmable fixture is
installed.
Verify if the power supply and fixture have the same voltage
specifications (i.e. 12V and 12V, etc.).
Fixture does not dim Check that a compatible constant voltage dimmable fixture is
installed.
Verify that a compatible dimming control is installed and
wired correctly.
Different fixture types do not dim in sync Each fixture type has its own circuit design and may respond
differently when dimmed. Check that each fixture type is
installed on a separate dimmable power supply for best
performance.
Fixture is flickering Verify that a compatible dimming control is installed. If
flickering occurs at low light levels install a compatible
dimming control with low-end dial adjustment
(i.e. Lutron
®
C•L).
Check that a compatible constant voltage dimmable fixture is
installed.
Check that all connections are properly secured.
Check if fixture is receiving the correct input voltage.
Check to make sure power supply is not wired to a dimmed
receptacle.
Fixture is steadily (continuous) ashing Check that the power supply is not overloaded. An
overloaded power supply will cause the auto-reset to trip
repeatedly.
Installation trips main breaker Check wiring for any short circuits. If breaker continues to
trip there may be a short in the power supply. Call customer
service for a replacement unit.
Troubleshooting
!
Do not attempt to ground this unit. It is double-insulated. Keep? 7/17 Yes 8/17
This unit can be mounted in any orientation, horizontal or vertical.
Power Supply provides shut down protection against short circuit,
over loading, and over temperature. Unit automatically recovers after
fault condition is removed and after cooling.
Intended for dry or damp locations only. Not intended for wet locations.
Not intended for recessed installation in ceilings or softs.
If any modication is made to the Power Supply, it will invalidate the
warranty and may render the product unsafe.
Tresco Lighting by Rev-A-Shelf
12400 Earl Jones Way
Louisville, KY 40299
T
el: 800-227-1171
Fax: 502-491-2215
Email: cservice@trescolighting.com
Web: www.trescolighting.com
I-DCE3060D-1, 11/19
I-PSREC-1 218 < This was the Proximity Form No.
LISTED
Save these instructions for future reference.
For technical assistance, call 1-800-227-1171
Page 2