User guide

2 - 2
NBOX(B)/PNC2 Printer Node Controller Installation Instructions TG200266 Issue 1/C 21/07/04
NBOX(B)/PNC2 Installation Instructions - Configuration
T X R X
O K
D T R B
D T R A
C T S BC T S A
J 1 3
J 1 2
Check Node Controller
13
Check supply
PNC2 Faulty
b (watchdog)
a (power)
(green)
(red)
Close flap
12
a
b
Set Battery Links On
11
T X R X
O K
D T R B
D T R A
C T S BC T S A
J 1 3
J 1 2
J 1 3
J 1 2
O N O N
O F F O F F
if NBOXB
Note: Batteries must be
charged for 16 hours
before they will support
unit during mains failure
0
I
Switch On
10
Set up printer
9
Set printer RS232 serial interface as follows:
Baud rate set as step 7 above (1k2, 4k8, 9k6, or 19k2)
Comms type set as step 8 above
either 8 bits no parity
or 7 bits odd parity
Auto Line Feed: On
2.1 Installation - Configuration (continued)
Set Dumb/Normal switch to Printer Comms Type
8
A D D R E S S
O N
D U M B
N O R M
Norm
Sets Printer Comms Type to:
7 bits odd parity
Dumb
Sets Printer Comms Type to:
8 bits no parity
e.g.