LONTERMINATOR Installation Instructions
LONTERMINATOR Installation Instructions TG200230 Issue 2 28/05/08
2
Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com
© 2008 Honeywell Technologies Sàrl, ECC Divison. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof
without obligation to notify any person of such revisions or changes.
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 21888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
WEEE Directive :
At the end of their useful life the packaging
and product should be disposed of by a
suitable recycling centre.
Do not dispose of with normal household waste.
Do not burn.
If FTT-10A or LPT10
Connect LONWORKS Network
4
T e r m i n a t o r
T e r m i n a t o r
T e r m i n a t o r
* Terminate LONWORKS bus at one end only
*
*
*
100 F, 50V minμ
100 F, 50V minμ
52.3 ±1%, 1/8 WΩ
Do not allow wires to
cross on a loop
terminate at LINC
or Router/Repeater
polarity independent
If used with LPT-10 (powered bus), cable lengths differ - see
“Link Power Transceiver User’s Guide (078-0105-01C)”.
elbaC
elbaCxaM
htgnel
otedonxaM
edon
20158nedleB)sdy545(m005)sdy545(m005
metsySQI
002/FH/61/0/1/PT
)1748nedleB(
)sdy545(m005)sdy034(m004
GWA22,VIleveLLU)sdy545(m005)sdy034(m004
8.0x2x2Y)tS(YJ)sdy545(m005)sdy053(m023
GWA42
,5.taCA865AIT)sdy094(m054)sdy072(m052
1, 2
or
3, 4
1
2
3
4
LONWORKS bus
Disposal