3.3.3 One Solids Separator and One Trapzilla
A single Trapzilla Solids Separator and Trapzilla Grease Interceptor should be installed in series. Place
Two-Way Cleanouts before, between and after the units as shown below. Make sure to connect an outlet
vent after the Trapzilla Grease Interceptor. If needed, a Low Head Flow Control (LHFC) is included with
Trapzilla Grease Interceptors (Not included with Solids Separators) or may be purchased separately
and should only be installed after the rst Cleanout and before the 4” Flow Splitter.
Note: Drawing for reference only. Equipment must be installed in
compliance with all applicable laws, regulations and codes, including
plumbing codes. Installation should be performed by a qualied
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SO
LE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739
Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1
°
CHECKED
SIZE
REV. NO.
DWG NO.
PART NO.
C
SCALE
RELEASE DATE
SHEET OF
ENGINEERING
DRAWN
DATE
THIRD ANG LE PROJECTIO N
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Outlet
Inlet
Cleanout*
Cleanout*
Cleanout*
Trapzilla
TZ-600 unit
Trapzilla
TSS-95 unit
*Use a Two-Way Cleanout before and after all
Trapzilla Installations
3.3.4 One Solids Separator and Two Trapzilla Units
A single Trapzilla Solids Separator and two Trapzilla Grease Interceptors should be installed by
placing the Solids Separator in line and then using a Flow Splitter to divert the water ow to two
separate Trapzilla units in parallel. Place Two-Way Cleanouts before, between and after the units
as shown below, including before and after the ow splitter. Make sure to connect an outlet vent
after the Trapzilla Grease Interceptor. If needed, a Low Head Flow Control (LHFC) is included with
Trapzilla Grease Interceptors (Not included with Solids Separators) or may be purchased separately
and should only be installed after the rst Cleanout and before the 4” Flow Splitter.
Note: Drawing for reference only. Equipment must be installed in
compliance with all applicable laws, regulations and codes, including
plumbing codes. Installation should be performed by a qualied
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SO
LE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739
Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1
°
CHECKED
SIZE
REV. NO.
DWG NO.
PART NO.
C
SCALE
RELEASE DATE
SHEET OF
ENGINEERING
DRAWN
DATE
THIRD ANG LE PROJECTIO N
Outlet
Outlet
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Inlet
Trapzilla
TSS-95 unit
Trapzilla
TZ-600 unit
Trapzilla
TZ-600 unit
Outlet Vent
(Connect to
facility vent)
4" (100mm) Flow Splitter
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
*Use a Two-Way Cleanout before and after all
Trapzilla Installations
Flow Splitter