3.3 Plumbing Congurations
3.3.1 One Solids Separator
Trapzilla Solids Separators DO NOT ship with a Low Head Flow Control module. If needed, it may be
purchased separately and installed to the inlet of the Trapzilla and connected to a code-approved air
intake.
Thermaco, Inc. recommends installation of 4” (100 mm) Two-Way Cleanouts on both the Inlet and
Outlet of Trapzilla
®
Models TSS-70 and TSS-95 in accordance with all applicable laws, regulations
and codes. A Vent on the Outlet piping is also to be installed in accordance with all applicable laws,
regulations and codes.
Note: Drawing for reference only. Equipment must be installed in
compliance with all applicable laws, regulations and codes, including
plumbing codes. Installation should be performed by a qualied
*Use a Two-Way Cleanout
before and after all Trapzilla
Installations
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SO
LE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739
Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1
°
CHECKED
SIZE
REV. NO.
DWG NO.
PART NO.
C
SCALE
RELEASE DATE
SHEET OF
ENGINEERING
DRAWN
DATE
THIRD ANG LE PROJECTIO N
Outlet
Inlet
*Cleanout
*Cleanout
Outlet Vent
(Connect to
facility vent)
3.3.2 Two Solids Separators
Two Trapzilla Solids Separators should be installed in parallel with a Flow Splitter diverting the ow.
Place Two-Way Cleanouts before, between and after the units as shown below, including before and
after the ow splitter. Make sure to connect an outlet vent after each Trapzilla Grease Interceptor. If
needed, a Low Head Flow Control (LHFC) may be purchased separately and should only be installed
after the rst Cleanout and before the 4” Flow Splitter.
Note: Drawing for reference only. Equipment must be installed in
compliance with all applicable laws, regulations and codes, including
plumbing codes. Installation should be performed by a qualied
1
1
2
2
3
3
4
4
A A
B B
C C
D D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SO
LE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739
Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1
°
CHECKED
SIZE
REV. NO.
DWG NO.
PART NO.
C
SCALE
RELEASE DATE
SHEET OF
ENGINEERING
DRAWN
DATE
THIRD ANG LE PROJECTIO N
Cleanout*
Cleanout*
Cleanout*
Cleanout*
Outlet
Outlet
Inlet
Trapzilla
TZ-600 unit
Trapzilla
TZ-600 unit
*Use a 4" (100 mm) Two-Way Cleanout for TSS-70,
TSS-95, TZ-400 and TZ-600 Unit Installations
Outlet Vent
(Connect to
facility vent)
4" (100 mm) Flow Splitter
*Use a Two-Way Cleanout before and after all
Trapzilla Installations
Flow Splitter