User's Manual

1
3
FOCUS Electric Meter
Refer to Landis & Gyr documentation for operational information on the FOCUS electric
meters.
Note: Certain functions of the M2e radio are only available on certain FOCUS models. This
section will identify these functions.
M2e AMR Operations
The M2e radio is a full transceiver. Its standard mode of operation is to transmit its standard
data packet on a regular interval. This standard data packet contains the following
information:
Meter ID
Meter Read (kWh+)
Data Flags
Meter Read (kWh-)
The M2e radio standard transmit interval is 3 seconds.
After each transmission, the M2e radio turns on its receiver and listens for any command
coming from the mobile system transceiver. These commands can be for configuration or
datalogging. This is the mode of handshaking for 2-way communications.
M2e Datalogging
Via the G2 Mobile software, the user can request the following datalogs:
kWh Consumption (60 min intervals)
Instantaneous Voltage (1 min intervals)
Instantaneous Power (1 min intervals)
The data is stored in CSV files on the G2 Mobile laptop for viewing and analysis.
M2e Configuration
Via the G2 Mobile software, the user can perform data verifications and re-configuration of
the M2e settings.
The Landis & Gyr FOCUS meters also have an infrared port which allows a “passthrough”
mode. Utilizing the L&G IR module, the user can perform a configuration of the radio.