Installation and Maintenance Manual

Table Of Contents
UV-SVN03F-EN 87
Maintenance
Service Access
To access the unit for water balancing, motor access or
other start-up and maintenance functions, use one of the
following methods:
1. Remove the end pocket front panel.
2. Remove the return air grille by releasing the mounting
screws.
3. If there is no shelving or oth
er obstructions, removing
the end panel may allow more access.
Periodic Maintenance
The following maintenance suggestions apply to all types
of unit ventilators, chilled water, hot water, split systems
and electric. Additional information for controls not
supplied by The Trane Company should be obtained from
the controls manufacturer.
Split system unit ventilators include a condensing unit and
the instructions provided with the condensing unit will
apply to the entire refrigerant system.
Filters. The air filters supplied with Trane UVs are
specially designed for high lint content. Depending upon
room conditions, these filters will normally need to be
replaced every four to eight weeks. To assure proper unit
operation, inspect the filters monthly and clean or replace
as required.
Overloaded filters will reduce unit air handling capacity,
which may result in insufficient heating during the
morning warm-up period and loss of natural cooling
capacity during mild weather.
Filter Replacement. The air filter on the vertical unit is
located near the bottom of the unit. Filter sizing may be
found in Table 5, p. 11.
1. To remove the filters, take-off the air sections front
panel.
2. Slide the filter out of the filter
rack on the bottom of the
unit.
3. Replace old filter with new
filter and re-attach front
panel.
Cleaning of the Drain Pan. The unit ventilators drain
pan is removable for periodic cleaning or easy access for
maintenance/drainage issues. Use Figure 60 and
Figure 61, p. 88, and the following steps for removing the
drain pan.
1. Turn off power to the unit and remove the front panel.
2. Disconnect the condensate drai
n line from the P-trap.
3. Disconnect fan plug.
4. Remove (4) pan clips located at each end of the pans
front
.
5. Disconnect the fan board ground wire and slide out fan
boa
rd (see Figure 60).
6. Remove drain pan for cleaning (see Figure 61, p. 88).
7. When reinstalling, re
verse sequence.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could
result in exposure to electrical, mechanical or other
potential safety hazards. Always refer to the safety
warnings provided throughout this manual concerning
these procedures. When possible, disconnect all
electrical power including remote disconnects before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
NOTICE:
Equipment Damage!
Do not operate unit without filters or grilles in place.
Failure to do so may cause equipment failure.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Figure 60. Slide out fan board
UV-SVN03_.book Page 87 Thursday, January 24, 2013 5:27 PM