Installation and Maintenance Manual

Table Of Contents
Installation—Sensors
32 UV-SVN03F-EN
b. Secure the back plate against the mounting surface
using included hardware.
4. To install the zone sensor module to a standard
junction box:
a. Level and install a 2 x 4-in.
junction box (installer
supplied) vertically on the wall.
b. Pull the control wires through the cutout. Attach the
module to the wall using the screws provided.
5. Strip the insulation on the interconnection wires back
0.25-inch and connect to TB1 (for wired sensors).
6. Screw down the terminal bloc
ks (for wired sensors).
7. To replace the cover:
a. Hook the cover over the top of the
back plate. Apply
light pressure to the bottom of the cover until it
snaps in place.
b. Install the security screw into the bottom of the
cover (if desired).
If installing a Tracer ZN520 zone sensor, see “Control
Options,” p. 29 for more information.
Figure 37.
Figure 38.
Wireless Sensors
Notes:
Receivers ship installed on the unit. To remove the
receiver, press in the retention tabs on the underside of
the receiver enclosure and push upward.
For more detailed information for wireless sensors,
please refer to BAS-SVX04E-EN (Installation,
Operation, and Maintenance: Wireless Sensors,
Models WTS, WZS, and WDS), or the most recent
revision.
Address Setting
The process of establishing communication between a
receiver and sensor is referred to as association. The
following limitations apply:
Each associated receiver/sensor set that
com
municates within the reception range of the
wireless system must have a unique address.
It is not possible to associate more than one sensor to a
receiver, nor is it possible to associate more than one
receiver to a sensor.
To associate a receiver and sensor, the two devices must
have their rotary address switches set to the same
address.
Important: Set the addresses before applying power to
the receiver and before removing the
insulation strip (Figure 39) from the sensor.
To set the receiver and sensor addresses:
1. Using a small screwdriver, set the three rotary address
switches (locations S1, S2, S3) on the receiver to an
address between 001 and 999 (see Figure 39). You do
Security
screw
UV-SVN03_.book Page 32 Thursday, January 24, 2013 5:27 PM