Mechanical Specifications
• Occupancy override to allow the tenant to request temporary timed override system operation
that keeps the building conditions in occupied comfort conditions.
• COMM module that is compatible with all Trane
®
wired temperature sensors. This accessory
provides a local RJ22 connection to Trane
®
service tools for easy, low-cost maintenance.
Filter
Units equipped with a standard throwaway filter have an average resistance of 76 percent and dust
holding capacity of 26 grams per square foot.
Units equipped with 1-in. MERV 8 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with
ASHRAE Standard 52.1 atmospheric dust spot method.
Units equipped with 1-in. MERV 13 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and
greater than 90 percent efficiency on 3–10 micron particles when tested in accordance with
ASHRAE Test Standard 52.2.