Dimensional Data
Note: 1-3/8 in. OD and 2-1/8 in. OD crossover piping
Crossover piping is available for all 2- or 4-pipe coils selections. Trane provides the crossover
for the hot water only. The crossover pipe is factory-insulated with 3/8 in.-thick insulation.
Expansion compensation between the factory piping package and the crossover piping is
achieved using a flex hose rated at 250 psi working pressure. Flex hose is only available with
factory-mounted piping packages.
Expansion compensation for the crossover piping must be handled external to the unit
ventilator.
Crossover connections terminate in the same end pocket as the heating coil on all 2- and 4-pipe
coils.
FLUSH
FLUSH
1 1/2"
1 1/4"
3"
24"
19 3/8"
3 5/8"
5 3/8"
RETURN
7/8" I.D. FIELD
CONN. W/ SHUT
OFF VALVE
7/8" I.D. FIELD
CONN. W/ SHUT
OFF VALVE
RETURN
TOP VIEW
SIDE VIEW
TOP VIEW
SIDE VIEW
16 5/8" DEPTH UNIT
21 1/4" DEPTH UNIT
SUPPLY
3"
24"
19 3/8"
3 1/2"
4 1/2"
8 1/4"
10"
SUPPLY
RS
3 1/2"
4 1/2"
RS
Crossover Piping