Catalogue
UV-PRC003-EN 59
Performance Data
Table 41. VUV 150, cooling coil J (DX)
Size EWB
Suct
Temp
EDB = 70°F EDB = 75°F EDB = 80°F EDB = 85°F
TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB
1500 61 40 41.7 27.5 53.0 51.1 45.6 36.3 52.5 50.0 50.5 44.5 52.4 48.6 56.5 52.2 52.7 46.9
45 34.9 25.0 54.5 52.8 38.2 33.0 54.6 51.9 42.4 40.5 54.9 50.8 47.3 47.3 55.7 49.4
50 28.2 22.5 56.1 54.5 30.9 29.7 56.6 53.8 34.2 34.2 58.8 52.9 38.2 38.2 61.3 51.9
64 40 49.5 23.7 55.3 52.8 52.2 33.4 54.3 52.1 55.5 42.4 53.7 51.2 59.7 51.0 53.4 50.0
45 41.5 21.6 56.6 54.8 43.7 30.4 56.2 54.2 46.5 38.6 56.1 53.5 50.1 46.4 56.3 52.5
50 33.5 19.4 58.0 56.7 35.3 27.3 58.1 56.2 37.6 34.7 58.5 55.6 40.4 40.4 60.0 54.9
67 40 58.6 19.0 58.2 54.5 60.5 29.2 56.9 53.9 62.7 38.9 55.9 53.3 65.6 48.2 55.1 52.5
45 49.1 17.3 59.3 56.8 50.7 26.6 58.5 56.3 52.6 35.4 58.1 55.8 55.0 43.8 57.9 55.2
50 39.7 15.5 60.4 58.9 40.9 23.9 60.2 58.6 42.4 31.8 60.3 58.2 44.4 39.4 60.6 57.7
70 40 70.1 24.1 60.1 55.7 71.7 34.2 58.8 55.2 73.6 44.0 57.7 54.7
45 58.8 21.9 61.4 58.3 60.1 31.1 60.7 58.0 61.7 40.0 60.2 57.5
50 47.4 19.7 62.8 60.8 48.5 28.0 62.7 60.5 49.8 36.0 62.7 60.2
73 40 82.0 28.6 62.3 57.1 83.3 38.6 61.1 56.7
45 68.7 26.0 63.9 60.0 69.8 35.1 63.3 59.7
50 55.4 23.4 65.5 62.8 56.4 31.6 65.4 62.6
EDB = Entering Air Temperature, Dry Bulb (°F)
EWB = Entering Air Temperature, Wet Bulb (°F)
TC = Total Capacity (MBh)
SC = Sensible Capacity (MBh)
LDB = Leaving Air Temperature, Dry Bulb (°F)
LWB = Leaving Air Temperature, Wet Bulb (°F)
Table 42. Airflow correction (% of design airflow)
%
Total Capacity
(MBh)
Sensible Capacity
(MBh)
120 1.025 1.105
110 1.012 1.051
100 1.000 0.998
90 0.987 0.945
80 0.974 0.892
Table 43. Airflow through coil J
Unit Model 1500
Rated cfm 1495+
Cooling - 150 - Coil (DX)
UV-PRC003-EN.book Page 59 Tuesday, June 4, 2013 8:59 PM