Catalogue
UV-PRC003-EN 55
Performance Data
Table 37. VUV 150, cooling coil E, 3-row / 16 fpi
Entering
Wet Bulb
Temp
(°F)
Entering
Dry Bulb
Temp
(°F)
Entering
Water
Temp
(°F)
Flow Rate (gpm)
6 8 10 14
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
61 70 40 31.8 23.1 11.0 37.7 25.4 9.7 42.2 27.2 8.7 48.2 29.5 7.1
42 30.1 22.4 10.4 35.5 24.6 9.2 39.7 26.1 8.2 45.2 28.3 6.6
45 27.4 21.2 9.5 32.3 23.2 8.4 36.0 24.6 7.4 40.6 26.4 6.0
48 24.8 20.1 8.7 29.0 21.9 7.6 32.2 23.1 6.7 36.0 24.6 5.3
75 40 34.7 30.0 12.0 41.1 33.0 10.6 46.0 35.2 9.4 52.6 38.3 7.7
42 32.8 29.0 11.3 38.7 31.8 10.0 43.3 33.9 8.9 49.3 36.7 7.2
45 29.9 27.5 10.4 35.2 30.1 9.1 39.2 31.9 8.1 44.3 34.3 6.5
48 27.0 26.0 9.4 31.6 28.3 8.2 35.1 29.9 7.3 39.2 31.9 5.8
80 40 38.5 36.3 13.2 45.5 39.9 11.7 51.0 42.6 10.4 58.3 46.4 8.5
42 36.4 35.1 12.5 43.0 38.5 11.0 48.1 41.0 9.8 54.7 44.4 8.0
45 33.2 33.2 11.5 39.1 36.4 10.1 43.5 38.6 8.9 49.2 41.5 7.2
48 30.0 30.0 10.4 35.1 34.3 9.1 38.9 36.2 8.0 43.5 38.6 6.4
85 40 42.9 42.2 14.7 50.8 46.4 13.0 57.0 49.6 11.6 65.1 53.9 9.5
42 40.6 40.6 13.9 48.0 44.8 12.3 53.6 47.7 11.0 61.0 51.6 8.9
45 37.0 37.0 12.7 43.6 42.4 11.2 48.6 44.9 9.9 54.9 48.3 8.0
48 33.5 33.5 11.6 39.2 39.2 10.1 43.4 42.1 8.9 48.6 44.9 7.1
90 40 47.9 47.8 16.3 56.7 52.6 14.5 63.5 56.1 12.9 72.6 61.1 10.5
42 45.2 45.2 15.5 53.5 50.8 13.7 59.8 54.0 12.2 68.0 58.5 9.9
45 41.3 41.3 14.2 48.6 48.0 12.4 54.1 50.9 11.1 61.2 54.7 8.9
48 37.3 37.3 12.8 43.7 43.7 11.2 48.4 47.7 9.9 54.1 50.9 7.9
67 75 40 43.4 24.9 14.9 51.4 27.4 13.1 57.6 29.2 11.8 65.8 31.8 9.6
42 41.0 24.1 14.1 48.5 26.4 12.4 54.2 28.1 11.1 61.7 30.5 9.0
45 37.4 22.9 12.9 44.1 25.0 11.3 49.1 26.5 10.1 55.5 28.5 8.1
48 33.8 21.6 11.7 39.6 23.5 10.2 43.9 24.8 9.0 49.1 26.5 7.2
80 40 45.5 32.2 15.6 53.9 35.4 13.8 60.4 37.8 12.3 69.0 41.2 10.0
42 43.0 31.2 14.7 50.8 34.2 13.0 56.9 36.4 11.6 64.7 39.4 9.4
45 39.3 29.6 13.5 46.2 32.3 11.9 51.5 34.3 10.5 58.2 36.8 8.5
48 35.5 28.0 12.2 41.5 30.4 10.7 46.0 32.2 9.4 51.5 34.3 7.5
85 40 48.5 39.3 16.6 57.4 43.3 14.6 64.3 46.2 13.1 73.5 50.2 10.7
42 45.8 38.1 15.7 54.1 41.7 13.8 60.5 44.4 12.3 68.9 48.1 10.0
45 41.8 36.1 14.3 49.2 39.5 12.6 54.8 41.8 11.2 61.9 45.0 9.0
48 37.8 34.1 13.0 44.2 37.2 11.4 49.0 39.3 10.0 54.8 41.9 8.0
90 40 52.0 46.2 17.7 61.6 50.8 15.7 69.0 54.3 14.0 78.8 59.0 11.4
42 49.2 44.7 16.8 58.1 49.1 14.8 65.0 52.2 13.2 73.9 56.6 10.7
45 44.9 42.4 15.4 52.8 46.4 13.5 58.8 49.2 12.0 66.5 52.8 9.7
48 40.5 40.1 13.9 47.5 43.7 12.2 52.6 46.1 10.8 58.8 49.2 8.6
70 75 40 49.4 21.8 16.9 58.5 24.0 14.9 65.5 25.6 13.3 74.9 27.8 10.9
42 46.7 21.1 16.0 55.2 23.1 14.1 61.7 24.6 12.6 70.2 26.7 10.2
45 42.6 20.0 14.6 50.1 21.9 12.8 55.9 23.2 11.4 63.1 24.9 9.2
48 38.5 18.9 13.2 45.1 20.6 11.6 49.9 21.7 10.2 55.9 23.2 8.2
80 40 50.7 29.3 17.3 60.1 32.2 15.3 67.3 34.4 13.7 76.9 37.4 11.2
42 48.0 28.3 16.4 56.7 31.1 14.5 63.4 33.1 12.9 72.1 35.8 10.5
45 43.8 26.9 15.0 51.5 29.4 13.2 57.4 31.1 11.7 64.8 33.5 9.4
48 39.5 25.4 13.6 46.3 27.6 11.9 51.3 29.2 10.5 57.4 31.2 8.4
85 40 52.9 36.6 18.0 62.7 40.3 16.0 70.2 43.0 14.3 80.3 46.8 11.6
42 50.0 35.5 17.1 59.1 38.9 15.1 66.1 41.4 13.5 75.3 44.8 10.9
45 45.7 33.6 15.6 53.8 36.8 13.7 59.9 39.0 12.2 67.7 41.9 9.8
48 41.3 31.8 14.2 48.3 34.6 12.4 53.5 36.6 10.9 59.9 39.0 8.7
90 40 55.8 43.9 19.0 66.1 48.3 16.8 74.0 51.5 15.0 84.6 56.1 12.3
42 52.8 42.5 18.0 62.3 46.6 15.9 69.7 49.6 14.2 79.4 53.7 11.5
45 48.1 40.3 16.4 56.7 44.0 14.5 63.1 46.7 12.9 71.3 50.2 10.4
48 43.5 38.1 14.9 50.9 41.5 13.0 56.4 43.8 11.5 63.1 46.7 9.2
Cooling - 150 - Coil E