Catalogue

UV-PRC003-EN 51
Performance Data
Table 31. VUV 125, cooling coil J (DX)
Size EWB
Suct
Temp
EDB = 70°F EDB = 75°F EDB = 80°F EDB = 85°F
TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB
1250 61 40 35.1 23.4 52.7 51.0 38.4 30.9 52.2 49.9 42.5 37.8 52.1 48.5 47.5 44.3 52.3 46.8
45 29.4 21.2 54.3 52.8 32.2 28.1 54.2 51.9 35.6 34.4 54.6 50.8 39.8 39.8 55.6 49.4
50 23.7 19.1 55.9 54.5 25.9 25.3 56.3 53.8 28.7 28.7 58.8 52.9 32.1 32.1 61.3 51.8
64 40 41.7 20.2 55.1 52.8 43.9 28.4 54.0 52.0 46.7 36.1 53.3 51.1 50.2 43.4 52.9 49.9
45 34.9 18.3 56.5 54.8 36.8 25.8 55.9 54.2 39.1 32.8 55.8 53.4 42.1 39.4 55.9 52.5
50 28.2 16.5 57.8 56.7 29.7 23.2 57.9 56.2 31.6 29.5 58.2 55.6 34.0 34.0 59.9 54.9
67 40 49.3 16.2 58.0 54.4 50.9 24.9 56.6 53.9 52.8 33.1 55.5 53.3 55.1 41.0 54.7 52.5
45 41.3 14.7 59.1 56.7 42.7 22.6 58.3 56.2 44.2 30.1 57.8 55.8 46.2 37.2 57.5 55.1
50 33.3 13.2 60.2 58.9 34.4 20.3 60.0 58.5 35.7 27.1 60.0 58.1 37.3 33.5 60.2 57.6
70 40 59.0 20.5 59.9 55.6 60.3 29.1 58.5 55.2 61.9 37.4 57.4 54.6
45 49.4 18.6 61.3 58.3 50.5 26.4 60.5 57.9 51.9 34.0 59.9 57.5
50 39.9 16.8 62.6 60.8 40.8 23.8 62.4 60.5 41.9 30.6 62.4 60.1
73 40 68.9 24.3 62.0 57.0 70.1 32.8 60.8 56.6
45 57.8 22.1 63.7 60.0 58.7 29.8 63.0 59.7
50 46.6 19.9 65.3 62.8 47.4 26.9 65.1 62.5
EDB = Entering Air Temperature, Dry Bulb (°F)
EWB = Entering Air Temperature, Wet Bulb (°F)
TC = Total Capacity (MBh)
SC = Sensible Capacity (MBh)
LDB = Leaving Air Temperature, Dry Bulb (°F)
LWB = Leaving Air Temperature, Wet Bulb (°F)
Table 32. Airflow correction (% of design airflow)
%
Total Capacity
(MBh)
Sensible Capacity
(MBh)
120 1.025 1.105
110 1.012 1.051
100 1.000 0.998
90 0.987 0.945
80 0.974 0.892
Table 33. Airflow through coil J
Unit Model 1250
Rated CFM 1253
Cooling - 125 - Coil (DX)
UV-PRC003-EN.book Page 51 Tuesday, June 4, 2013 8:59 PM