Performance Data
Table 21. VUV 100, cooling coil J (DX)
Size EWB
Suct
Temp
EDB = 70°F EDB = 75°F EDB = 80°F EDB = 85°F
TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB TC SC LDB LWB
1000 61 40 29.1 19.1 52.1 50.5 31.8 25.3 51.3 49.3 35.2 31.0 51.0 47.9 39.4 36.3 51.0 46.0
45 24.4 17.4 53.7 52.3 26.7 23.0 53.5 51.4 29.5 28.1 53.7 50.2 33.0 33.0 54.1 48.7
50 19.7 15.6 55.4 54.1 21.5 20.7 55.6 53.4 23.8 23.8 57.7 52.5 26.6 26.6 60.1 51.3
64 40 34.6 16.5 54.6 52.1 36.4 23.2 53.3 51.4 38.7 29.5 52.4 50.4 41.6 35.5 51.8 49.1
45 29.0 15.0 56.0 54.2 30.5 21.1 55.2 53.6 32.5 26.8 54.9 52.8 34.9 32.2 54.9 51.8
50 23.4 13.5 57.4 56.3 24.6 19.0 57.2 55.8 26.2 24.1 57.4 55.2 28.2 28.2 58.6 54.4
67 40 40.9 13.2 57.6 53.7 42.2 20.3 56.0 53.1 43.7 27.1 54.6 52.5 45.7 33.5 53.6 51.6
45 34.3 12.0 58.8 56.1 35.4 18.5 57.7 55.6 36.7 24.6 57.0 55.1 38.3 30.5 56.4 54.4
50 27.7 10.8 59.9 58.4 28.5 16.6 59.5 58.1 29.6 22.2 59.2 57.6 30.9 27.4 59.3 57.1
70 40 48.9 16.8 59.3 54.8 50.0 23.8 57.7 54.3 51.3 30.6 56.4 53.7
45 41.0 15.2 60.8 57.6 41.9 21.6 59.8 57.2 43.0 27.8 59.0 56.7
50 33.1 13.7 62.2 60.2 33.8 19.5 61.7 60.0 34.7 25.0 61.6 59.6
73 40 57.2 19.9 61.4 56.0 58.1 26.9 59.8 55.6
45 47.9 18.1 63.1 59.2 48.7 24.4 62.2 58.9
50 38.7 16.2 64.8 62.2 39.3 22.0 64.4 61.9
EDB = Entering Air Temperature, Dry Bulb (°F)
EWB = Entering Air Temperature, Wet Bulb (°F)
TC = Total Capacity (MBh)
SC = Sensible Capacity (MBh)
LDB = Leaving Air Temperature, Dry Bulb (°F)
LWB = Leaving Air Temperature, Wet Bulb (°F)
Table 22. Airflow correction (% of design airflow)
%
Total Capacity
(MBh)
Sensible Capacity
(MBh)
120 1.025 1.105
110 1.012 1.051
100 1.000 0.998
90 0.987 0.945
80 0.974 0.892
Table 23. Airflow through coil J
Unit Model 1000
Rated cfm 989
Cooling - 100 - Coil (DX)
UV-PRC003-EN.book Page 43 Tuesday, June 4, 2013 8:59 PM