Catalogue

UV-PRC003-EN 37
Performance Data
Table 15. VUV 075, hydronic heating coils A (1-row / 12 fpi), B (2-row / 12 fpi), C (2-row / 16 fpi)
Coil
Entering
Air Temp,
Dry Bulb
(°F)
Entering
Water
Temp (°F)
Flow Rate (gpm)
246
Total
Capacity
(MBh)
Waterside
Temp Drop
(°F)
Total
Capacity
(MBh)
Waterside
Temp Drop
(°F)
Total
Capacity
(MBh)
Waterside
Temp Drop
(°F)
A 50 120 19.7 19.0 22.9 11.1 24.3 7.9
140 27.5 26.8 32.1 15.7 34.1 11.1
160 35.5 34.8 41.4 20.4 43.9 14.4
180 43.5 42.8 50.8 25.1 53.7 17.7
55 120 18.6 17.9 21.7 10.5 23.0 7.4
140 26.0 25.3 30.4 14.9 32.2 10.5
160 33.5 32.8 39.2 19.3 41.5 13.6
180 41.2 40.5 48.0 23.7 50.8 16.7
60 120 17.5 16.8 20.4 9.9 21.7 7.0
140 24.6 23.9 28.7 14.0 30.4 9.9
160 31.6 30.9 36.9 18.1 39.2 12.8
180 38.8 38.1 45.3 22.3 47.9 15.7
65 120 16.5 15.8 19.2 9.3 20.4 6.6
140 23.1 22.4 26.9 13.1 28.6 9.3
160 29.7 29.0 34.7 17.0 36.8 12.0
180 36.5 35.8 42.6 21.0 45.1 14.8
70 120 15.4 14.7 18.0 8.7 19.1 6.1
140 21.6 20.9 25.2 12.3 26.7 8.7
160 27.8 27.1 32.5 15.9 34.4 11.2
180 34.2 33.5 39.8 19.6 42.2 13.8
B 50 120 27.3 26.6 34.4 16.9 37.6 12.3
140 38.4 37.7 48.5 23.9 52.9 17.4
160 49.7 49.0 62.7 31.0 68.2 22.5
180 61.2 60.5 77.0 38.2 83.7 27.7
55 120 25.9 25.2 32.5 15.9 35.5 11.6
140 36.3 35.6 45.9 22.6 50.0 16.4
160 47.0 46.3 59.3 29.3 64.6 21.3
180 57.9 57.2 72.8 36.1 79.2 26.2
60 120 24.4 23.7 30.7 15.0 33.5 10.9
140 34.3 33.6 43.3 21.3 47.2 15.5
160 44.4 43.7 55.9 27.6 60.9 20.1
180 54.6 53.9 68.7 34.0 74.7 24.7
65 120 22.9 22.2 28.9 14.1 31.5 10.3
140 32.2 31.5 40.7 20.0 44.4 14.6
160 41.7 41.0 52.6 26.0 57.3 18.9
180 51.4 50.7 64.6 32.0 70.2 23.2
70 120 21.5 20.8 27.0 13.2 29.5 9.6
140 30.1 29.4 38.1 18.7 41.5 13.6
160 39.0 38.3 49.2 24.3 53.6 17.6
180 48.1 47.4 60.4 29.9 65.7 21.7
C 50 120 28.3 27.6 36.1 17.7 39.5 12.9
140 39.9 39.2 50.9 25.1 55.5 18.3
160 51.7 51.0 65.7 32.5 71.6 23.6
180 63.6 62.9 80.7 40.0 87.8 29.0
55 120 26.8 26.1 34.2 16.8 37.3 12.2
140 37.7 37.0 48.1 23.7 52.5 17.3
160 48.9 48.2 62.2 30.8 67.8 22.4
180 60.2 59.5 76.3 37.8 83.1 27.5
60 120 25.3 24.6 32.2 15.8 35.2 11.5
140 35.6 34.9 45.4 22.4 49.5 16.3
160 46.1 45.4 58.7 29.0 63.9 21.1
180 56.8 56.1 72.0 35.7 78.4 25.9
65 120 23.8 23.1 30.3 14.8 33.1 10.8
140 33.5 32.8 42.7 21.0 46.6 15.3
160 43.3 42.6 55.1 27.2 60.1 19.8
180 53.4 52.7 67.7 33.5 73.7 24.3
70 120 22.2 21.5 28.3 13.8 31.0 10.1
140 31.3 30.6 39.9 19.6 43.6 14.3
160 40.6 39.9 51.6 25.5 56.2 18.5
180 50.0 49.3 63.4 31.4 68.9 22.7
Heating - 075 - Coil A, B, C