Catalogue
36 UV-PRC003-EN
Performance Data
Table 12. VUV 075, cooling coil J (DX)
Size EWB
Suct
Temp
EDB = 70°F EDB = 75°F EDB = 80°F EDB = 85°F
TC SC LDBLWBTC SC LDBLWBTC SC LDBLWBTC SC LDBLWB
750 61 40 22.8 15.0 51.4 50.0 25.0 19.9 50.4 48.8 27.7 24.3 49.9 47.2 30.9 28.5 49.7 45.4
45 19.1 13.7 53.0 52.0 20.9 18.1 52.6 51.0 23.2 22.1 52.6 49.7 25.9 25.9 52.9 48.2
50 15.4 12.3 54.8 53.8 16.9 16.2 54.9 53.1 18.7 18.7 56.9 52.1 20.9 20.9 59.1 50.9
64 40 27.1 13.0 53.9 51.6 28.6 18.3 52.3 50.8 30.4 23.2 51.3 49.8 32.7 27.9 50.5 48.5
45 22.7 11.8 55.4 53.9 23.9 16.6 54.5 53.2 25.5 21.1 53.9 52.3 27.4 25.3 53.7 51.3
50 18.3 10.6 56.9 56.0 19.3 14.9 56.6 55.5 20.6 19.0 56.5 54.8 22.1 22.1 57.6 54.0
67 40 32.1 10.4 57.1 53.1 33.1 16.0 55.2 52.5 34.3 21.3 53.6 51.8 35.9 26.3 52.4 50.9
45 26.9 9.4 58.4 55.7 27.8 14.5 57.1 55.1 28.8 19.3 56.1 54.6 30.1 23.9 55.4 53.9
50 21.7 8.5 59.5 58.1 22.4 13.1 58.8 57.7 23.2 17.4 58.5 57.2 24.3 21.5 58.4 56.7
70 40 38.4 13.2 58.7 54.1 39.2 18.7 56.9 53.6 40.3 24.0 55.3 53.0
45 32.2 12.0 60.1 57.0 32.9 17.0 59.0 56.6 33.7 21.9 57.9 56.2
50 26.0 10.8 61.6 59.8 26.5 15.3 61.1 59.5 27.2 19.7 60.6 59.2
73 40 44.8 15.6 60.7 55.3 45.6 21.1 58.9 54.8
45 37.6 14.2 62.4 58.6 38.2 19.2 61.2 58.3
50 30.3 12.8 64.2 61.8 30.8 17.3 63.6 61.5
EDB = Entering Air Temperature, Dry Bulb (°F)
EWB = Entering Air Temperature, Wet Bulb (°F)
TC = Total Capacity (MBh)
SC = Sensible Capacity (MBh)
LDB = Leaving Air Temperature, Dry Bulb (°F)
LWB = Leaving Air Temperature, Wet Bulb (°F)
Table 13. Airflow correction (% of design airflow)
%
Total Capacity
(MBh)
Sensible Capacity
(MBh)
120 1.025 1.105
110 1.012 1.051
100 1.000 0.998
90 0.987 0.945
80 0.974 0.892
Table 14. Airflow through coil J
Unit Model 0750
Rated cfm 748
Cooling - 075 - Coil (DX)
UV-PRC003-EN.book Page 36 Tuesday, June 4, 2013 8:59 PM