Catalogue
UV-PRC003-EN 35
Performance Data
Table 11. VUV 075, cooling coil H, 3-row / 16 fpi
Entering
Wet Bulb
Temp
(°F)
Entering
Dry Bulb
Temp
(°F)
Entering
Water
Temp
(°F)
Flow Rate (gpm)
24610
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
ΔT
(°F)
61 70 40 13.8 10.5 14.5 20.1 12.7 10.4 23.2 13.8 8.0 26.1 14.9 5.4
42 13.2 10.3 13.8 19.0 12.3 9.8 21.8 13.3 7.5 24.6 14.2 5.0
45 12.1 9.9 12.8 17.2 11.7 8.9 19.8 12.5 6.8 22.2 13.3 4.6
48 11.0 9.5 11.7 15.4 11.1 8.0 17.6 11.8 6.1 19.7 12.4 4.1
75 40 15.0 13.6 15.7 21.9 16.5 11.3 25.3 17.9 8.7 28.5 19.2 5.8
42 14.3 13.3 15.0 20.7 15.9 10.7 23.8 17.2 8.2 26.8 18.4 5.5
45 13.2 12.8 13.9 18.8 15.1 9.7 21.5 16.2 7.4 24.2 17.2 5.0
48 12.0 12.0 12.7 16.8 14.3 8.7 19.2 15.2 6.6 21.5 16.1 4.4
80 40 16.7 16.4 17.4 24.3 19.9 12.5 28.1 21.7 9.6 31.6 23.3 6.5
42 15.9 15.9 16.6 22.9 19.3 11.8 26.4 20.8 9.0 29.7 22.3 6.1
45 14.7 14.7 15.4 20.8 18.3 10.8 23.9 19.6 8.2 26.8 20.9 5.5
48 13.3 13.3 14.0 18.6 17.4 9.6 21.3 18.5 7.3 23.8 19.5 4.9
85 40 18.6 18.6 19.3 27.1 23.2 13.9 31.3 25.2 10.7 35.3 27.1 7.2
42 17.8 17.8 18.4 25.6 22.4 13.1 29.5 24.2 10.1 33.1 25.9 6.8
45 16.4 16.4 17.1 23.2 21.3 12.0 26.7 22.8 9.1 29.9 24.3 6.1
48 14.9 14.9 15.6 20.8 20.2 10.7 23.7 21.5 8.1 26.6 22.7 5.5
90 40 20.8 20.8 21.4 30.3 26.3 15.5 34.9 28.6 11.9 39.3 30.7 8.0
42 19.8 19.8 20.5 28.5 25.4 14.6 32.9 27.5 11.2 37.0 29.4 7.5
45 18.3 18.3 18.9 25.9 24.1 13.3 29.7 25.8 10.1 33.3 27.5 6.8
48 16.6 16.6 17.3 23.2 22.9 11.9 26.5 24.3 9.1 29.6 25.7 6.1
67 75 40 18.8 11.3 19.5 27.4 13.7 14.1 31.7 14.9 10.8 35.6 16.0 7.3
42 17.9 11.0 18.6 25.9 13.2 13.3 29.8 14.3 10.2 33.5 15.3 6.8
45 16.5 10.7 17.2 23.5 12.6 12.1 27.0 13.5 9.2 30.2 14.3 6.2
48 15.0 10.2 15.7 21.0 11.9 10.8 24.0 12.7 8.2 26.9 13.4 5.5
80 40 19.8 14.6 20.4 28.8 17.7 14.7 33.2 19.2 11.3 37.4 20.7 7.6
42 18.8 14.3 19.5 27.2 17.1 13.9
31.3 18.5 10.7 35.2 19.8 7.2
45 17.4 13.8 18.0 24.6 16.2 12.7 28.3 17.4 9.7 31.7 18.5 6.5
48 15.8 13.3 16.5 22.0 15.4 11.4 25.2 16.4 8.6 28.2 17.3 5.8
85 40 21.0 17.8 21.7 30.6 21.6 15.7 35.4 23.5 12.0 39.8 25.3 8.1
42 20.0 17.4 20.7 28.9 20.9 14.8 33.3 22.6 11.3 37.4 24.2 7.6
45 18.5 16.8 19.2 26.2 19.8 13.5 30.1 21.3 10.3 33.8 22.6 6.9
48 16.8 16.2 17.5 23.5 18.8 12.1 26.8 20.0 9.2 30.0 21.1 6.1
90 40 22.6 20.9 23.2 32.9 25.4 16.8 38.0 27.6 12.9 42.7 29.7 8.7
42 21.5 20.5 22.2 31.0 24.6 15.9 35.7 26.5 12.1 40.2 28.4 8.2
45 19.8 19.8 20.5 28.2 23.3 14.4 32.3 25.0 11.0 36.2 26.6 7.4
48 18.0 18.0 18.7 25.2 22.1 12.9 28.8 23.5 9.8 32.2 24.8 6.6
70 75 40 21.4 9.9 22.1 31.2 12.0 16.0 36.0 13.0 12.2 40.6 14.0 8.3
42 20.4 9.7 21.1 29.5 11.6 15.1 33.9 12.5 11.5 38.1 13.4 7.8
45 18.8 9.3 19.5 26.7 11.0 13.7 30.7 11.8 10.5 34.4 12.5 7.0
48 17.1 9.0 17.8 23.9 10.4 12.3 27.3 11.1 9.3 30.6 11.7 6.3
80 40 22.0 13.3 22.7 32.1 16.1 16.4 37.0 17.5 12.6 41.7 18.8 8.5
42 21.0 13.0 21.7 30.3 15.6 15.5 34.8 16.8 11.8 39.2 18.0 8.0
45 19.3 12.5 20.0 27.5 14.8 14.1 31.5 15.8 10.7 35.3 16.8 7.2
48 17.6 12.0 18.3 24.6 14.0 12.6 28.1 14.9 9.6 31.4 15.7 6.4
85 40 23.0 16.6 23.7 33.5 20.1 17.1 38.6 21.9 13.1 43.5 23.5 8.8
42 21.9 16.3 22.6 31.6 19.5 16.1 36.4 21.0 12.4 40.9 22.5 8.3
45 20.2 15.7 20.9 28.7 18.5 14.7 32.9 19.8 11.2 36.9 21.1 7.5
48 18.4 15.1 19.0 25.6 17.5 13.2 29.3 18.6 10.0 32.8 19.7 6.7
90 40 24.2 19.9 24.9 35.3 24.1 18.0 40.7 26.2 13.8 45.8 28.2 9.3
42 23.1 19.5 23.8 33.3 23.3 17.0 38.3 25.2 13.0 43.1 27.0 8.8
45 21.3 18.8 22.0 30.2 22.1 15.4 34.7 23.7 11.8 38.9 25.2 7.9
48 19.4 18.1 20.0 27.0 21.0 13.8 30.9 22.3 10.5 34.5 23.6 7.0
Cooling - 075 - Coil H
UV-PRC003-EN.book Page 35 Tuesday, June 4, 2013 8:59 PM