UniTrane® Fan-Coil Air Terminal Devices Horizontal, Vertical, and Low Vertical Sizes 02-12 Basic Series Fan-Coil, Sizes 04-08 December 2000 UNT-PRC001-EN
It isn’t just a fan and a coil… The Trane Company has redesigned the traditional fan-coil to lead the industry in: • indoor air quality (IAQ) features • easy installation and maintenance • high quality and durability • advanced controls Smaller unit footprint Factory installed and tested controls Quiet operation Two, three or four-row coils Factory assembled, installed and tested piping package with IAQ drain pan to collect condensate Removable, noncorrosive, positively-sloped drain pan that’s easy to
Contents Basic UniTrane Introduction 2 Features and Benefits 64 4 Selection Procedure 65 5 Model Number Description 65 5 General Data 66 12 Performance Data 67 18 Two-Pipe Coils Four-Pipe Coils Hot Water Reheat Coils Steam Reheat Coils 67 68 Controls 69 19 22 25 28 31 Electrical Data 70 39 Dimensions and Weights 72 42 Mechanical Specifications 76 58 60 Options UNT-PRC001-EN 3
Features and Benefits The UniTrane® fan-coil meets the standards of today’s market, as well as the anticipated needs of tomorrow’s market. The tradition that company founder Reuben Trane began 60 years ago continues with the latest generation of fan-coils from The Trane Company.
Selection Procedure Model Number Description UniTrane Fan-Coil Model Number Description Following is a complete description of the fan-coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.
Selection Procedure Digit 26 — Filter 0 = None 1 = 1” Throwaway Filter 2 = 1” Throwaway Pleated Media Filter 3 = 1” Throwaway + (1) Extra 4 = 1” Throwaway Pleated Media + (1) Extra 5 = 1” Throwaway + (2) Extras 6 = 1” Throwaway Pleated Media + (2) Extras 7 = 1” Throwaway + (3) Extras 8 = 1” Throwaway Pleated Media + (3) Extras Digit 27 — Main Control Valve 0 = None A = 2-Way, 2-Position, NO (25 psig) B = 3-Way, 2-Position, NO (30 psig) C = 2-Way, 2-Position, NC (25 psig) D = 3-Way, 2-Position, NC (15 psig)
General Data Model A Vertical Concealed Outlet Top Duct Collar Inlet Front Toe Space Model B Vertical Cabinet Fresh Air Bottom or Back Outlet Top Quad Grille, Top Bar Grille Inlet Front Toe Space, Front Bar Grille UNT-PRC001-EN Unit Configurations Fresh Air Bottom or Back 7
General Data Unit Configurations Model C Horizontal Concealed Inlet Back Duct Collar Outlet Front Duct Collar Fresh Air N/A Fresh Air Top or Back Outlet Front Duct Collar Inlet Bottom Toe Space Inlet Open Return Outlet Front Duct Collar No Filter Fresh Air N/A 8 UNT-PRC001-EN
General Data Unit Configurations Model D Horizontal Cabinet Fresh Air Top or Back Fresh Air N/A Inlet Back Stamped Louver Outlet Front Quad Grille, Front Bar Grille Outlet Front Duct Collar Inlet Bottom Stamped Louver Fresh Air Top or Back Fresh Air N/A Inlet Back Duct Collar Outlet Front Duct Collar Inlet Bottom Stamped Louver Outlet Front Quad Grille, Front Bar Grille Fresh Air N/A Outlet Front Quad Grille, Front Bar Grille UNT-PRC001-EN Fresh Air N/A Inlet Back Duct Collar Inlet Back Stampe
General Data Unit Configurations Model E Horizontal Recessed Fresh Air Top or Back Outlet Front Duct Collar Inlet Bottom Stamped Louver Fresh Air N/A Inlet Back Duct Collar Outlet Front Duct Collar Outlet Top Duct Collar Model H Vertical Recessed Fresh Air Bottom or Back Inlet Front Stamped Louver Outlet Front Stamped Louver Fresh Air Bottom or Back Inlet Front Stamped Louver 10 UNT-PRC001-EN
Unit Configurations General Data Model J Vertical Cabinet Slope Top Outlet Top Quad Grille, Top Bar Grille Inlet Front Toe Space, Front Bar Grille Model K Low Vertical Concealed Fresh Air Bottom or Back Outlet Top Duct Collar Fresh Air Back Inlet Front Toe Space Model L Low Vertical Cabinet Outlet Top Quad Grille, Top Bar Grille Fresh Air Back Inlet Front Bar Grille UNT-PRC001-EN 11
General Data Table GD-1. UniTrane® Fan-Coil General Data Unit Size Coil Data Face Area — Ft2 (cm2) LxDxH — In. (cm) 2-Row 3-Row 4-Row Volume — Gal. (Liters) 1-Row (Heat) 2-Row 3-Row 4-Row Fins/Ft (cm) 2-Row 3-Row 4-Row Reheat Coil Data (1-Row) Hot Water or Steam Face Area — Ft2 (cm2) LxDxH — In. (cm) Volume — Gal. (Liters) Fins/Ft (cm) Fan/Motor Data Fan Quantity Size — Dia” x Width” (cm) 02 03 04 06 08 10 12 0.8 (743) 0.8 (743) 1.1 (1020) 1.6 (1490) 2.1 (1950) 3.2 (2970) 3.2 (2970) 15x1.
General Data Table GD-3. Fan-Coil Air Flow FC 02 03 04 06 08 10 12 Motor Coil 2R144 3R144 4R144 2R144 3R144 4R144 2R144 3R144 4R144 2R144 3R144 4R144 2R144 3R144 4R144 2R144 3R144 4R144 2R144 3R144 4R144 FD 0.05 240 230 200 320 310 280 390 370 340 610 610 560 800 730 680 980 1000 930 1110 1080 1000 ESP High Static 0.1 330 330 300 410 400 370 450 550 510 760 890 820 1020 1000 940 1260 1400 1300 1430 1520 1430 0.
Factory-Installed Piping Packages UniTrane® fan-coils have standard piping packages available as a factory built and installed option, for the main coil. Piping package options are also available for the hot water reheat coil on two-pipe units equipped with either a fan speed switch or Tracer® ZN.520 controller. Factory built assures all piping packages are fully tested under water for leaks and are built within strict tolerances.
General Data Manual Circuit Setter In lieu of a ball valve on the leaving water pipe, a manual circuit setter, also known as a manual flow control valve, acts as both a flow setting device and a stop valve. This valve allows water flow through the fan-coil unit to be set quickly and accurately. The manual circuit setter includes Schrader ports in the valve body. These ports are used to measure the pressure drop across the valve.
General Data Piping Packages Automatic Circuit Setter (C) 16 UNT-PRC001-EN
General Data Selecting the Correct Modulating Valve Size Modulating valves are available in any of four port sizes. These four port sizes relate to a Cv of 0.7, 1.5, 2.5 or 4.0, which is the coefficient of flow. The coefficient of flow is defined as the volume of water flow through a control valve in the fully open position with a 1 psig (6.895 kPa) differential across the valve.
Two-Pipe Coils Performance Data UniTrane® fan-coil performance data is submitted to ARI with units grouped based on performance. Unit performance is impacted by the unit model and the airflow inlet and outlet configuration. Below is a table which summarizes the performance groups. Table PD-1.
Performance Data Two-Pipe Coils ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-2.
Two-Pipe Coils Performance Data ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-4.
Performance Data Two-Pipe Coils ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115 V, 0.2” (0.05 kPA) ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-6.
Four-Pipe Coils Performance Data ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-8.
Performance Data Four-Pipe Coils ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-10.
Four-Pipe Coils Performance Data ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) DT. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) DT. All performance measured on high speed tap, 115V, 0.2” (0.05 kPA) ESP with a throwaway filter. See page 18 for performance groupings. Table PD-12.
Performance Data Hot Water Reheat Coils The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3 or 4-row cooling coil. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 20 F (-7 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-14.
Performance Data Hot Water Reheat Coils The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3 or 4-row cooling coil. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 20 F (-7 C) DT. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings. Table PD-16.
Performance Data Hot Water Reheat Coils Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 20 F (-7 C) DT. All performance measured on high speed tap, 115 V, 0.2” (.5 cm) ESP, with no filter. See page 18 for performance groupings. Table PD-18. Hot Water Reheat Coil With High Static Motor, Group 2 Main Coil FC Rows 2 02 3 4 2 03 3 4 2 04 3 4 2 06 3 4 2 08 3 4 2 10 3 4 2 12 3 4 TMBH (TkW) 3.1 (.9) 3.0 (.9) 2.9 (.8) 4.3 (1.3) 4.0 (1.2) 3.
Performance Data Steam Reheat Coils Table PD-20. Steam Properties Steam Pressure PSIG (kPa) Sat. Steam Temp. F (C) Latent Heat — BTU/LB. (kJ/kg) 2 (14) 219 (104) 965 (2240) 5 (34) 227 (108) 960 (2230) 10 (69) 239 (115) 952 (2210) 15 (103) 250 (121) 945 (2200) Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. Table PD-21.
Performance Data Steam Reheat Coils Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure. All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. Table PD-23. Steam Reheat Coil With Free Discharge Motor, Group 3 FC 02 03 04 06 08 10 12 Main Coil Rows 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 psig (14 kPa) TMBH (TkW) 4.7 (1) 4.6 (1) 4.4 (1) 6.1 (2) 6.0 (2) 5.8 (2) 7.9 (2) 7.7 (2) 7.
Performance Data Steam Reheat Coils Heating performance is based on 70 F (21 C) entering air temperature, 2 psig (14 kPa) and 5 psig (103 kPa) entering steam pressure. All performance measured on high speed tap, 115 V, 0.2” (.5 cm) ESP, with no filter. Table PD-25. Steam Reheat Coil With High Static Motor, Group 2 FC 02 03 04 06 08 10 12 Main Coil Rows 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 psig (14 kPa) TMBH (TkW) 5.6 (2) 5.5 (2) 5.3 (2) 7.2 (2) 6.8 (2) 6.6 (2) 8.7 (3) 9.5 (3) 9.3 (3) 13.
Controls Control Options UniTrane® fan-coils are available with four different control options: • Manual three-speed fan switch • Tracer ZN.010 • Tracer ZN.510 • Tracer ZN.520 Manual Fan Mode Switch Model Number Digit 30 = A and Digit 31 = D or K The manual fan mode switch is available for fan-coil units that do not have Trane factory-mounted control packages. This four-position switch (off, high, medium,low) allows manual fan mode selection and is available unit or wall mounted.
Controls Sequence of Operation Fan Speed Switch Off: Fan is turned off, two-position damper option spring-returns closed. option cycles to maintain setpoint temperature. Fresh air damper option is open. High, Medium, Low: Fan runs continuously at the selected speed. The twoposition damper option opens to an adjustable mechanical stop-position. ZN.520 Off: Fan is off; control valve options and fresh air damper options close. The low air temperature detection option is still active. ZN.010 and ZN.
Controls General Information Table C-1. Controller Input/Output Summary ZN.010 ZN.510 ZN.
Controls Zone Sensor Options Zone Sensor Options Zone sensors are available as either unit, wall, or split-mounted options for design flexibility. Fan-coils with the unit-mounted zone sensor option include a thermistor in the unit’s return air path. Wall-mounted zone sensor options have an internal thermistor. Zone sensors operate on 24 VAC. ZN.
Controls Control Features The following control functions are standard features on units with Tracer ZN.010, ZN.510, or ZN.520. Entering Water Temperature Sampling Function A system that uses a two-way control valve option might not sense the correct entering water temperature during long periods when the control valve is closed. If the demand for heating or cooling does not exist for a long period, the entering water will eventually approach ambient temperature.
Controls ZN.520 Additional Features Automatic Ventilation Reset To ensure proper ventilation rates, the controller is configured with two fresh air damper minimum position setpoints for occupied operation. As the fan speed changes to low or high, the damper modulates to maintain the correct ventilation rate for the space. The damper position does not change when the fan speed changes to medium. Fan Status The ZN.520 controller monitors the fan output status to determine if the fan is operating.
Controls End Device Options All end device options are factoryinstalled and tested. Two-Position Control Valves Model Number Digits 27 and 28 = A - H Two-position valve options are available with either Tracer ZN.010, ZN.510, or ZN.520. Valves are spring-return type, sweat connections, and available as normally open or closed. The valves respond to a 24V signal and have 1/2-inch sweat connections. The two-way valve option will either fully open or close.
Controls Control Valve Economizer Fresh Air Damper Actuator (ZN.520) Model Number Digit 13 = G, H, or J This option is a three-wire floating point, spring-return damper actuator and is factory-wired and mounted to the damper assembly. When the controller enables the economizer and the unit is in occupied mode, the fresh air damper modulates between its minimum position (editable) and the full open position to maintain setpoint temperature.
Electric Heat Electrical Data Table ED-1. Electric Heat kW Unit Size 02 03 04 06 08 10 12 Unit Voltage 115 230 277 208 115 230 277 208 115 230 277 208 115 230 277 208 115 230 277 208 115 230 277 208 115 230 277 208 kW 1.0 1.0 1.0 0.8 1.0 1.0 1.0 0.8 kW 1.5 1.5 1.5 1.1 1.5 1.5 1.5 1.1 kW 2.0 2.0 2.0 1.5 2.0 2.0 2.0 1.5 2.0 2.0 2.0 1.5 2.0 2.0 2.0 1.5 2.0 2.0 2.0 1.5 kW 1.9 2.5 2.5 2.5 1.9 2.5 2.5 2.5 1.9 kW 2.3 3.0 3.0 3.0 2.3 3.0 3.0 3.0 2.3 3.0 3.0 3.0 2.3 3.0 3.0 3.0 2.3 3.0 3.0 3.0 2.
Electrical Data Table ED-3. Free Discharge Motors on Units with Two-Row Coils 115 Volt FC 02 03 04 06 08 10 FLA 0.6 0.7 0.9 1.2 1.4 0.9 12 0.9 1.2 HP (kW) .03 (.02) .04 (.02) .05 (.04) .07 (.05) .12 (.09) .05 (.04) 1.4 .05 (.04) .07 (.05) FLA 0.3 0.4 0.5 0.6 0.9 0.5 208-230 Volt HP (kW) .03 (.02) .04 (.02) .05 (.04) .07 (.05) .12 (.09) 0.6 .05 (.04) .07 (.05) FLA 0.2 0.3 0.4 0.5 0.6 0.4 277 Volt HP (kW) .03 (.02) .04 (.02) .05 (.04) .07 (.05) .12 (.09) 0.5 .05 (.04) .07 (.05) .12 (.09) 0.
Electrical Data Table ED-7. Low Vertical Free Discharge Motors (115 Volt) FC 03 FLA 0.7 HP (kW) .03 (0) 04 0.8 .03 (0) 06 1.1 .03 (0) H M L H M L H M L RPM 1090 770 560 1090 750 560 1115 760 560 Note: Actual rpm will vary with application and configuration. Table ED-8. Decimal to Fractional HP (kW) Conversion FC 02 03 04 06 08 10 12 Low Vertical 03, 04, 06 Decimal .03 .07 .04 .05 .08 .05 .06 .10 .13 .07 .12 .16 .24 .12 .13 .24 .05 .07 .06 .12 .10 .16 .13 .24 .05 .12 .06 .13 .10 .24 .13 .
Dimensions and Weights Unit Weights Table DW-1. Operating Weights — lbs.
Dimensions and Weights Vertical Concealed Vertical Concealed, Model A Vertical Concealed Unit Dimensions Unit Size 02-03 04 A 2’-8 11/16” 3’-1 11/16” B 1’-9 5/16” 2’-2 5/16” C 1’-10 13/16” 2’-3 13/16” D 1’-5 5/16” 1’-10 5/16” E 1’-7 5/16” 2’-0 5/16” 06 3’-11 3/16” 2’-11 13/16” 3’-1 5/16” 2’-7 13/16” 2’-9 13/16” 08 4’-7 11/16” 3’-8 5/16” 3’-9 13/16” 3’-4 5/16” 3’-6 5/16” 10-12 6’-2 11/16” 5’-3 5/16” 5’-4 13/16” 4’-11 5/16” 5’-1 5/16” NOTE:1.
Dimensions and Weights Vertical Cabinet Vertical Cabinet, Model B Vertical Cabinet Unit Dimensions Unit Size A B C D E F 02-03 2’-9 5/16” 1’-9 5/16” 7 5/8” 1’-6” 1’-7 5/16” 3’-5 5/16” 04 3’-2 5/16” 2’-2 5/16” 7 1/8” 2’-0” 2’-0 5/16” 3’-10 5/16” 06 3’-11 3/16” 2’-11 3/16” 8 7/8” 2’-6” 2’-9 13/16” 4’-7 3/16” 08 4’-8 5/16” 3’-8 5/16” 7 1/8” 3’-6” 3’-6 5/16” 5’-4 5/16” 10-12 6’-3 5/16” 5’-3 5/16” 7 5/8” 5’-0” 5’-1 5/16” 6’-11 5/16” NOTE:1.
Dimensions and Weights Horizontal Concealed Horizontal Concealed, Model C Horizontal Concealed Unit Dimensions Unit Size 02-03 A 2’-8 11/16” B 1’-9 5/16” C 1’-10 13/16” D 1’-7 3/8” E 1’-6 1/8” F 1’-7 5/16” 04 3’-1 11/16” 2’-2 5/16” 2’-3 13/16” 2’-0 3/8” 1’-11 1/8” 2’-0 5/16” 06 3’-11 3/16” 2’-11 13/16” 3’-1 5/16” 2’-9 7/8” 2’-8 5/8” 2’-9 13/16” 08 4’-7 3’-8 3’-9 3’-6 3’-5 3’-6 11 /16” 5 /16” 13 /16” 3 /8” 1 /8” 5 /16” 10-12 6’-2 11/16” 5’-3 5/16” 5’-4 13/16” 5’-1 3/8” 5’-0 1/8” 5’-1 5/16” NOTE:1.
Horizontal Cabinet Dimensions and Weights Horizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions Unit Size A B C D E F G H J 02-03 2’-9 5/16” 1’-9 5/16” 7 5/8” 1’-6” 1’-5 1/4” 3’-5 5/16” 8 5/8” 1’ -4” 1’-7 3/4” 04 3’-2 5/16” 2’-2 5/16” 7 1/8” 2’-0” 1’-10 1/4” 3’-10 5/16” 8 1/8” 1’-10” 1’-11 3/4” 06 08 3’-11 3/16” 4’-8 5/16” 2’-11 13/16”3’-8 5/16” 8 7/8” 7 1/8” 2’-6” 3’-6” 2’-7 3/4” 3’-4 1/4” 4’-7 3/16” 5’-4 5/16” 9 7/8” 8 1/8” 2’-4” 3’-4” 2’-7 3/4” 3’-3 3/4” 10-12 6’-3 5/16” 5’-3 5/16” 7 5/8”
Dimensions and Weights Horizontal Recessed, Model E Horizontal Recessed Horizontal Recessed Unit Dimensions Unit Size 02-03 A 2’-11 13/16” B 1’-9 5/16” C 1’-10 13/16” D 1’-7 3/8” E 1’-6 1/8” F 2’-8 7/16” G 2’-10 5/16” H 1’-7 3/4” 04 3’-4 13/16” 2’-2 5/16” 2’-3 13/16” 2’-0 3/8” 1’-11 1/8” 3’-1 7/16” 3’-3 5/16” 1’-11 3/4” 06 4’-2 5/16” 2’-11 13/16” 3’-1 5/16” 2’-9 7/8” 2’-8 5/8” 3’-10 15/16” 4’-0 13/16” 2’-7 3/4” 08 4’-10 13/16” 3’-8 5/16” 3’-9 13/16” 3’-6 3/8” 3’-5 1/8” 4’-7 7/16” 4’-9 5/16” 3’-3 3/4” 1
Dimensions and Weights Vertical Recessed Vertical Recessed, Model H Vertical Recessed Unit Dimensions Unit Size 02-03 A 2’-8 11/16” B 1’-9 5/16” C 1’-10 13/16” D 1’-5 5/16” E 3’-11” F 2’-6” G 2 3/8” H 3’-6” J 2’-2 1/2” 04 3’-1 11/16” 2’-2 5/16” 2’-3 13/16” 1’-10 5/16” 4’-3” 2’-6” 2 3/8” 4’-0” 2’-2 1/2” 06 3’-11 3/16” 2’-11 13/16” 3’-1 5/16” 2’-7 13/16” 5’-3” 2’-6” 2 3/8” 4’-9” 2’-2 1/2” 08 4’-7 11/16” 3’-8 5/16” 3’-9 13/16” 3’-4 5/16” 5’-5 1/2” 2’-9 1/2” 4 1/8” 5’-3” 2’-3 1/2” 10-12 6’-2 11/16” 5’-3
Dimensions and Weights Vertical Slope Top Vertical Slope Top, Model J Vertical Slope Top Unit Dimensions Unit Size A B C D E F 02-03 2’-9 5/16” 1’-9 5/16” 7 5/8” 1’-6” 1’-7 5/16” 3’-5 5/16” 04 3’-2 5/16” 2’-2 5/16” 7 1/8” 2’-0” 2’-0 5/16” 3’-10 5/16” 06 3’-11 13/16” 2’-11 13/16” 8 7/8” 2’-6” 2’-9 13/16” 4’-7 13/16” 08 4’-8 5/16” 3’-8 5/16” 7 1/8” 3’-6” 3’-6 5/16” 5’-4 5/16” 10-12 6’-3 5/16” 5’-3 5/16” 7 5/8” 5’-0” 5’-1 5/16” 6’-11 5/16” NOTE:1.
Dimensions and Weights Low Vertical Concealed Low Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions Unit Size 03 A 3’-5 7/16” B 2’-2 1/4” C 2’-3 15/16” D 1’-10 5/16” E 2’-0 1/4” 04 4’-2 15/16” 2’-11 3/4” 3’-0 13/16” 2’-7 13/16” 2’-9 3/4” 06 4’-11 7/16” 3’-8 1/4” 3’-9 15/16” 3’-4 5/16” 3’-6 1/4” NOTE: 1. Coil connections are always on the drain pan side and opposite the control box. 2. Coil connections are 5/8” O.D. sweat. 3. All duct collar dimensions are to the outside of the collar.
Dimensions and Weights Low Vertical Cabinet Low Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions Unit Size 03 A 3’-10 15/16” B 2’-2 1/4” C 11 7/16” D 2’-0” E 2’-0 1/4” 04 4’-8 7/16” 2’-11 3/4” 1’-1 5/16” 2’-6” 2’-9 3/4” 06 5’-4 15/16” 3’-8 1/4” 11 7/16” 3’-6” 3’-6 1/4” NOTE: 1. Coil connections are always on the drain pan side and opposite the control box. 2. Coil connections are 5/8” O.D. sweat. 3. All duct collar dimensions are to the outside of the collar. 4.
Dimensions and Weights Coil Connections Coil Connections, Vertical Units Coil Connections, Horizontal Units RHR - Reheat Return RMS - Reheat Supply HR - Hot Water Return HS - Hot Water Supply CR - Chilled Return CS - Chilled Water Supply Note: Reheat coils are available with 2-pipe main coils only on units with either a fan speed switch or Tracer ZN.520 control.
Dimensions and Weights Fresh Air Opening Fresh Air Opening Locations Horizontal Units Models C, D, and E HORIZONTAL CONCEALED AND RECESSED HORIZONTAL CABINET Fresh Air Opening Dimensions, Horizontal Units Unit Size A B UNT-PRC001-EN 02-03 04 1’-6” 1’-11” 1’-9 5/16” 2’-2 5/16” 06 08 2’-8 1/2” 3’-5” 2’-11 13/16” 3’-8 5/16” 10-12 5’-0” 5’-3 5/16” 53
Dimensions and Weights Fresh Air Opening Fresh Air Opening Locations Vertical Units Models A, B, and J VERTICAL CONCEALED AND RECESSED VERTICAL CABINET AND SLOPE TOP Fresh Air Opening Dimensions, Vertical Units Unit Size A B 54 02-03 04 1’-6” 1’-11” 1’-9 5/16” 2’-2 5/16” 06 08 2’-8 1/2” 3’-5” 2’-11 13/16” 3’-8 5/16” 10-12 5’-0” 5’-3 5/16” UNT-PRC001-EN
Dimensions and Weights Fresh Air Opening Locations Low Vertical Units Models K and L Fresh Air Opening Fresh Air Opening Dimensions, Low Vertical Units Unit Size A B 03 2’-0 1/4” 2’-2 1/4” 04 2’-9 3/4” 2’-11 3/4” 06 3’-6 1/4” 3’-8 1/4” LOW VERTICAL CABINET REAR VIEW LOW VERTICAL CONCEALED REAR VIEW UNT-PRC001-EN 55
Dimensions and Weights Wall Box Wall Box CONTINUOUS MORTAR RIBS TOP AND BOTTOM Wall Box Dimensions Unit Size Ref. Only 02 - 03 04 06 08 10 -12 Dimensions AxB 24 3/8 x 4 3/4 3 24 /8 x 7 1/2 33 1/8 x 7 1/2 37 1/2 x 7 1/2 58 1/4 x 7 1/2 Internal Supports 1 1 2 3 4 /8” 1 1 /8 ” 1 /2 ” /4 ” 3 /2” 1 1 3/8” /8 ” 1 4” CLEARANCE FOR DRAINAGE CONTINUOUS DRIP LIP TOP AND BOTTOM 56 ADDITIONAL INTERNAL SUPPORTS EQUALLY SPACED. NOT TO EXCEED 12” O.C.
Dimensions and Weights Projection Panel Projection Panel Projection Panel Dimensions Unit Size A B 02 - 03 3’-11” 2’-6” 04 4’-3” 2’-6” 06 5’-3” 2’-6” UNIT TO WALL — TOP VIEW 08 5’-5 1/2” 2’-9 1/2” 10 - 12 7’-5 1/2” 2’-9 1/2” Projection Panel, All Unit Sizes C D E 2” 1 1/8“ 8 5/8“ 2 1/2” 1 5/8“ 8 1/8“ 3” 2 1/8“ 7 5/8“ 3 1/2” 2 5/8“ 7 1/8“ 4” 3 1/8“ 6 5/8“ 4 1/2” 3 5/8“ 6 1/8“ 5” 4 1/8“ 5 5/8“ 5 1/2” 4 5/8“ 5 1/8“ 6” 5 1/8“ 4 5/8“ FRONT VIEW ISO REAR VIEW ISO UNT-PRC001-EN 57
Mechanical Specifications UniTrane® Fan-Coil Mechanical Specifications Performance Data Capacity: Unit capacities are certified under Industry Room Fan-Coil Air Conditioner Certification Program in accordance with ARI Standard 440-97. Safety: All standard units are UL listed in the United States and Canada and comply with NFPA 90A requirements. Construction All Units The unit includes a chassis, coil(s), fan wheel(s), fan casing(s), fan board and motor(s).
Mechanical Specifications body from piping. Use some means, such as a pump and chiller bypass, to ensure the maximum closed off DP rating of the two-way valves is not exceeded. Three-Way, Two-Position Control Valves Normally open three-way, two-position valves are rated for a maximum 25 psig (207 kPa) pressure differential across the valves. Normally closed three-way twoposition valves are rated for a maximum pressure differential across the valves of 15 psig (103 kPa).
Mechanical Specifications Disconnect Switch A unit mounted disconnect switch is available as a standard option on all units. Colors Six decorator colors are available in a baked powder finish. For a color chart, contact your local Trane office for a copy of UNT-S-10. Extended End Pockets On vertical or horizontal cabinet units, an 8” (20 cm) extended end pocket is available on the piping end.
Mechanical Specifications Options False Backs False backs increase the depth of a vertical cabinet unit and provide a cavity through which to run piping behind the fan-coil unit. False backs are also an excellent application when installing a unit beneath a window sill that extends out past the front of the unit. False backs are 18-gauge steel construction and have the same paint finish as the unit. The false back is available in depths between 2”- 8” (5 - 20 cm) in 1” (2.
Mechanical Specifications Options Piping Components Ball Valve Part Lever Seat Packing Stem G-Nut Ball Ball Valve Material Steel, zinc plated Teflon Teflon Rod Brass Hex Brass Brass, chrome plated Retainer Brass Body Cast Brass Spec ASTM VTFE RTFE B16 B16 B16 B16 B584-C84400 Working Pressure 400 psi (2,758 kPa) Manual Circuit Setter Material Body — Forged Brass Alloy Trim — Forged Brass Alloy All Wetted Parts Brass Manual Circuit Setter Temperature 250 F MAX (121 C) Working Pressure 300 psi (2,069 k
Mechanical Specifications Options Control Valve Material Body — Forged Brass Stem — Chrome-Plated Brass (Modulating) Nickel Plated (2-Position) Seat — Brass (2-Position) Stainless Steel (Modulating) Paddle — Buna N (2-Position) Plug — High Temperature Thermoplastic (Modulating) Actuator — Stainless Steel Base Plate, Aluminum Cover Temperature 200 F MAX (93 C) Control Valve Working Pressure 300 psi (2,069 kPa) Pressure Drop (Close-Off ∆P)* 2-Way, Two-Position, N.O.
Features and Benefits Basic Series Fan-Coil Sizes 04-08 The basic series fan-coil design is for the market that requires only the basic features of our standard UniTrane® fancoil. Basic series units are horizontal concealed and are available with an exposed fan, plenum, or ceiling access panel.
Basic Series Model Number Selection Procedure Model Number Description Following is a complete description of the basic series fan-coil model number. Each digit in the model number has a corresponding alphanumeric code to identify the specific option.
General Data Basic Series Table B-GD-1. Coil Data Unit Size Face Area — Ft. (cm) LxDxH—In. (cm) 3-Row 4-Row Volume — Gal. (Liters) 1-Row (4-pipe only) 2-Row (4-pipe only) 3-Row 4-Row Fins per Ft. (cm) All coils 04 1.1 (1020) 06 1.6 (1490) 08 2.1 (1950) 20x2.6x8 (51x7x20) 20x3.5x8 (51x9x20) 29.5x2.6x8 (75x7x20) 29.5x3.5x8 (75x9x20) 38x2.6x8 (97x7x20) 38x3.5x8 (97x9x20) .08 (.30) .15 (.57) .23 (.87) .30 (1.14) .11 (.42) .22 (.83) .33 (1.25) .44 (1.67) .14 (.53) .28 (1.06) .42 (1.59) .56 (2.
Performance Data Basic Series Sizes 04-08 ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) ∆T. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) ∆T. All performance measured on high speed tap, free discharge motor at zero ESP, high static motor at 0.2 ESP, with throwaway filter, and is valid for all voltages except 208.
Basic Series Sizes 04-08 Performance Data ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a 10 F (5.5 C) ∆T. Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a 30 F (17 C) ∆T. All performance measured on high speed tap, free discharge motor at zero ESP, high static motor at 0.2 ESP, with throwaway filter, and is valid for all voltages except 208.
Controls Basic Series Accessories Manual Three-Speed Fan Switch The manual three-speed fan switch is a simple four-position switch (OFF-HI-MED-LO) which allows fan mode selection. The fan switch is wall-mounted and controls the fan motor by line voltage. Off: Fan is turned off. Hi, Med, Lo: Fan runs continuously at the selected speed setting.
Electrical Data Basic Series Electric Heat Electric Heat Features • All basic series fan-coil units are UL approved. • Units require only a single-point electrical connection. • A unit mounted magnetic contactor(s) is (are) supplied on all unit voltages. • A high temperature cutout with automatic reset de-energizes the electric heat in the event of an overheat condition. • When hydronic heating is active, a lockout sensor will disable the electric heat.
Electrical Data Basic Series Table B-ED-2. Three and Four-Row Coils — Free Discharge Motors 115 Volt FLA HP (kW) 1.0 .06 (.04) 1.4 .12 (.09) 1.7 .13 (.10) FC 04 06 08 208 Volt HP (kW) .06 (.04) 0.9 .12 (.09) 1.0 .13 (.10) FLA 0.6 H 108 RPM M 800 L 600 108 800 600 108 800 600 H 1580 RPM M 1375 L 1240 1475 1285 975 1475 1285 975 Table B-ED-3. Three and Four-Row Coils — High Static Motors 115 Volt FLA HP (kW) 2.1 .13 (.10) 3.4 .24 (.18) 3.4 .24 (.18) FC 04 06 08 208 Volt HP (kW) .
Dimensions and Weights Basic Series Table B-DW-1. Weights Unit Size 04 06 08 72 Shipping Weights — lbs. (kg) Model X Model P Model R 96 107 114 (44) (49) (52) 123 138 145 (56) (63) (66) 131 149 165 (59) (68) (75) Operating Weights — lbs.
Dimensions and Weights Basic Series Exposed Fan Basic Unit With Exposed Fan, Model X Unit Size 04 A 1 15/16” B 1’-5 1/16” C 1’-8 5/16” D 1’-10 3/16” E 2’-4 3/16” UNT-PRC001-EN 06 1 3/4” 2’-4 3/16” 2’-5 13/16” 2’-7 11/16” 3’-1 11/16” 08 5” 2’-6 3/16” 3’-2 5/16” 3’-4 3/16” 3’-10 3/16” Note: 1. The condensate drain connection is always on the right hand side of the unit as shown. 2. Coil connections are 5/8" OD sweat.
Dimensions and Weights Basic Series With Plenum Basic Unit With Plenum, Model P Unit Size 04 06 A 1’-8 11/16” 2’-6 3/16” B 1’-8 1/2” 2’-6” C 1’-8 5/16” 2’-5 13/16” D 1’-10 3/16” 2’-7 11/16” E 2’-4 1/4” 3’-1 3/4” 74 08 3’-2 11/16” 3’-2 1/2” 3’-2 5/16” 3’-4 3/16” 3’-10 1/4” Note: 1. The condensate drain connection is always on the right hand side of the unit as shown. 2. Coil connections are 5/8" OD sweat.
Dimensions and Weights Basic Series With Ceiling Panel Basic Unit With Ceiling Access Panel, Model R Unit Size 04 06 A 3’-1 7/16” 3’-10 15/16” B 3’-3 5/16” 4’-0 13/16” C 3’-4 13/16” 4’-2 5/16” UNT-PRC001-EN 08 4’-7 7/16” 4’-9 5/16” 4’-10 13/16” 75
Mechanical Specifications Basic Series Basic Series Fan-Coil Mechanical Specifications and is permanently lubricated. It is capable of starting at 78 percent of rated voltage and operating at 90 percent of rated voltage on all speed settings. The motor is run tested in assembled units. Capacity Unit capacities are certified under Industry Room Fan-Coil Air Conditioner Certification Program in accordance with ARI Standard 440-97. Safety All basic series units are UL listed.
Literature Order Number File Number The Trane Company A Division of American Standard Inc. www.trane.com For more information contact your local Trane office or e-mail us at comfort@trane.com Supersedes Stocking Location UNT-PRC001-EN PL -TD-UNT-PRC001-EN-1200 UNT-PRC001-EN 7/00 La Crosse - Inland Printing Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.