Installation and Maintenance Manual

Startup
UNT-SVX07D-EN 97
Binary Outputs (Tracer ZN520)
Binary outputs are configured to support the following:
Three fan stages (when one or two fan stages are
present, medium fan speed can be configured as
exhaust fan)
One hydronic cooling stage
One hydronic heating stage (dehumidification requires
th
is to be in the reheat position)
One DX cooling stage
One or two-stage electric heat
(dehumidification
requires this to be in the reheat position)
Face and bypass damper
Modulating outdoor air damper
One baseboard heat stage
For more information, see T
able 31, p. 97.
Zone Sensor (Tracer ZN520)
The Tracer ZN520 controller accepts the following zone
sensor module inputs:
Space temperature measurement (10kΩ thermistor)
Local setpoint (either internal or external on the zone
se
nsor module)
•Fan switch
Timed override (On) and Cancel timed override
Communication jack
Space Temperature Measurement (Tracer
ZN520)
Trane zone sensors use a 10kΩ thermistor to measure the
space temperature. Typically, zone sensors are wall-
mounted in the room and include a space temperature
thermistor. As an option, the zone sensor can be unit-
mounted with a separate space temperature thermistor
located in the unit’s return air stream. If both a hard-wired
and communicated space temperature value exist, the
Table 31. Binary output configuration (Tracer ZN520)
Binary
Output Configuration
J1-1 Fan high
J1-2 Fan medium
J1-3 Fan low
J1-4 (Key)
J1-5 Cool valve—open, or 2-position valve
(a)
(a)For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/
cool changeover, terminals J1-5 and J1-6 are used to control the pri-
mary valve for both heating and cooling. For Tracer ZN520 units con-
figured and applied as 2-pipe hydronic heat/cool changeover with
electric heat, terminals J1-5 and J1-6 are used to control the primary
valve (for both cooling and heating), and terminals J1-9 and J1-10 are
used only for the electric heat stage. For those 2-pipe changeover units,
electric heat will not be energized while the hydronic supply is hot (5°
or more above the space temperature).
J1-6 Cool valve—close Note 1
J1-9
Heat valve—open, or 2 position valve, or 1st electric heat
stage
(a)
J1-10 Heat valve—close or 2nd Electric heat stage
(a)
J1-11 Fresh air damper—open
J1-12 Fresh air damper—close
TB4-1 Generic/baseboard heat output
TB4-2 24 Vac
Table 32. Analog inputs (Tracer ZN520)
Descripti
on
Termina
ls Function Range
Zone TB3-1 Space temperature
input
5°F to 122°F
Ground TB3-2 Analog ground NA
Set TB3-3 Setpoint input 40°F to 115°F
Fan B3-4 Fan switch input 4821 to 4919 W (off)
2297 to 2342 W (auto)
10593 to 10807 W (low)
13177 to 13443 W
(medium)
15137 to 16463 W (high)
Ground TB3-6 Analog ground NA
Analog
input 1
J3-1 Entering water
temperature
-40°F to 212°F
J3-2 Analog ground NA
Analog
input 2
J3-3 Discharge air
temperature
-40°F to 212°F
J3-4 Analog ground NA
Analog
input 3
J3-5 Fresh air temp/generic
temp
-40°F to 212°F
J3-6 Analog ground NA
Analog
input 4
J3-7 Universal input 0% to 100%
Generic 4–20mA 0% to 100%
Humidity 0 to 2000 ppm
CO
2
J3-8 Analog ground NA
G r o u n d J 3 - 9 A n a l o g g r o u n d N A
Notes:
1. The zone sensor, entering water temperature sensor, discharge air
sensor, and the outside air temperature sensor are 10K thermistors.
2. Zone sensor: Wall-mounted sensors include a thermistor soldered to
the sensor’s circuit board. Unit mounted sensors include a return air
sensor in the units return air stream.
3. Changeover units include an entering water temperature sensor.
UNT-SVX07_-EN.book Page 97 Friday, April 27, 2012 9:40 AM