Note: Receivers ship installed on the unit. To remove the
receiver, press in the retention tabs on the
underside of the receiver enclosure (see Figure 32)
and push upward.
Note: For more detailed information for wireless sensors,
please see BAS-SVX04E-EN
Address Setting
The process of establishing communication between a
receiver and sensor is referred to as association. The
following limitations apply:
Each associated receiver/sensor set that
communicates within the reception range of the
wireless system must have a unique address.
It is not possible to associate more than one se
nsor to a
receiver, nor is it possible to associate more than one
receiver to a sensor.
To associate a receiver and sensor, the two devices must
have their rotary address switches set to the same
address.
Important: Set the addresses before applying power to
the receiver and before removing the
insulation strip (Figure 33) from the sensor.
To set the receiver and sensor addresses:
1. Using a small screwdriver, set the three rotary address
switches (locations S1, S2, S3) on the receiver to an
address between 001 and 999 (see Figure 33). You do
not have to remove the covers to access the rotary
address switches.
Note: Do not use 000 as an address. An address of
000 returns the receiver outputs to their factory
defaults (zone temperature and setpoint
outputs: 72.5°F, removes all association
knowledge, and prevents association with a
sensor.
2. Set the three rotary address switches (locations S1, S2,
S3
) on the sensor to the same address as the receiver
(see Figure 33).
Figure 32. Retention tabs on underside of receiver
enclosure
Figure 33. Setting the rotary address switches on the
receiver and the sensor
S5
GND
R77
C35
S1
S2
C33
LED4
S4
S5
S3
LED1
LED2
LED3
LED5
C34
J1
COMM -
24VAC/DC
SETPOINT
HEATING SET
SIGNAL
POWER
ADDDRESS
FAN/SYSTEM
ZONE
COMM +
INS
T
A
L
L
WIRELESS
GND
LED3
L
ED2
L
T
A
L
L
L
E
S
S
L
T
A
A
L
E
Receiver
DRESS
IN
B1 +
INSTALL
WIRELESS
S4
S3
S2
S1
ADDRESS
STATUS
BATTERY
LED5
SIGNAL
LED3
L
ED2
LED1
Pb
Pb-FREE
STATUS
LED4
Do not remove the
insulation strip yet.
Sensor