Installation and Maintenance Manual

ECM Overview and Setup
60 UNT-SVX07D-EN
Configuration parameter and value display
and modification changes
The ECM engine board’s on-board user interface is easy to
use and supports:
1. Verification/auditing of on-board parameter settings
(read-only)
2. Adjustment of the on-board settings (write)
The user interface has three input buttons, from left to
right:
1.
M enu /Set
2. “Decrement”
3. “Increment”
Each button has several different actuation levels
depending on length of press, and what the UI is currently
displaying.
Figure 28. User interface input buttons
Table 16. Button actuation levels
Button
Menu/Set
Duration Action
Short Press in
Status Display
<1 sec None
Short Press in
Configuration
Display
Toggles between parameter
name and value without saving
(abandons value if changed).
Long Press/Hold
in Status Display
>3 sec Enters the configuration menu
Long Press/Hold
in Configuration
Display
>3 sec If on a parameter name, toggles
to the value. If on a parameter
value, saves the value settings
and returns to the parameter
name as confirmation.
Button
Decrement
Duration Action
Short Press in
Status Display
<1 sec None
Short Press in
Configuration
Display
<1 sec Scrolls through parameter
names, or decreases value of
parameter.
Long Press/Hold
in Status Display
>3 sec N/A
Long Press/Hold
in Configuration
Display
>3 sec Faster scroll through parameter
name, or faster decrease of
values of parameters.
Button
Increment
Duration Action
Short Press in
Status Display
<1 sec None
Short Press in
Configuration
Display
<1 sec Scrolls through parameter
names, or increases value of
parameter.
Long Press/Hold
in Status Display
>3 sec N/A
Long Press/Hold
in Configuration
Display
Faster scroll through parameter
name, or faster increase of
values of parameters.