Installation and Maintenance Manual
ECM Overview and Setup
UNT-SVX07D-EN 59
RPM Mode
RUNNING/ FAN STATUS
CONTINUOUS LOOP
Displayed when:
1) No error codes are present
2) Motor has completed ramping
Indicates the current rpm of Motor 1 in the system. “0” rpm
here indicate that no fan speed has been requested.
→
Indicates the current rpm of Motor 2 in the system. “0” rpm
here indicate a fan off condition OR a fan “missing”
condition
(a)
.
→
Indicates the status being calculated or Fan Motor 1. If “off,”
this indicates that either:
1) No fan speed is being requested or
2) The fan performance is failing to meet the request; refer
to “Troubleshooting (ECM),” p. 126 for additional
information.
If “on,” this indicates that the fan is performing correctly and
will be used to report fan status correctly, depending on
mode.
/
Indicates the status being calculated or Fan Motor 2. If “off,”
this indicates that either:
1) No fan speed is being requested or
2) The fan performance is failing to meet the request; refer
to “Troubleshooting (ECM),” p. 126 for additional
information.
3) If the target speed for Motor 2 is “0,”this is used to
indicate a missing motor
(a)
.
If “on,” this indicates that the fan is performing correctly and
will be used to report fan status correctly, depending on
mode.
/
Indicates that the temperature sensing circuit has
calculated a logical “on” based on the settings of the
following parameters:
///
(a)Motor 1 is the only motor in sizes 200, 300, 400, 600, and 800. Sizes 1000 and 1200 units contain two motors: Motor 1 (single shaft) and Motor 2
(double shaft).
UNT-SVX07_-EN.book Page 59 Friday, April 27, 2012 9:40 AM