Installation and Maintenance Manual

ECM Overview and Setup
54 UNT-SVX07D-EN
ECM Engine Controller
The ECM engine controls and reports the performance
of up to two Trane BLDC motors.
The engine also co-ordinates the operation of the fan
in response to elec
tric heat behavior, and electric heat
behavior in response to hydronic heat behavior and
fan behavior.
The engine incorporates a user inter
face that allows
adjustment of certain unit parameters and provides
constant feedback on motor operation.
The engine integrates service and troubleshooting
to
ols, including high-precision tachometers, fan
status, and electric heat-enable indicators.
The engine integrates a versatile configurable
auxiliary
temperature sensor.
The engine incorporates various safety and lockout
features, suc
h as maintaining proper fan speeds, if
electric heat is called for.
Standard Adapter Board
The adapter allows direct customer interfacing
through the use of terminal strips. Standard
interfacing includes:
Fan Speeds (H, M, L) (for wall mounted fan speed
switc
hes)
Variable speed (0–10V) inputs
The standard adapter board elim
inates many separate
wiring harnesses in the panel and allows simple,
mistake-proofed single-plug interfacing of:
The ECM engine controller
–T
ransformers
–Motors
Valves
–Dampers
Electric heat control
Fan speed switches
Main Power (except electric heat).
Electric heat lockout circuits and fan proving circuits
for electric hea
t are standard, and are pre-configured at
the factory.
CSTI Adapter Board
Performs all the functions of the standard adapter
module, but in addition, provides convenient field
connections to factory mounted end devices,
including:
Valves
–D
ampers
Electric Heat
Performs courtesy
inversion” of thermostatic inputs
to match selected valves:
Figure 21. ECM engine controller
Figure 22. Adapter board
Note: Display and Menu/
Enter, Increase, and
Decrease Buttons
Note: Customer Low-
Voltage
Interface for
Fan Speeds,
Variable Fan
Speed, and
24 Vac Supply
Figure 23. CSTI adapter board
1. Customer Low-Voltage Interface for Valves, Electric Heat, Dampers, Fan
Speeds, Variable Fan Speed, and 24 Vac Supply
2. Valve(s), Electric Heat, and Changeover Configuration Switches (Factory-
Set)
1
2
UNT-SVX07_-EN.book Page 54 Friday, April 27, 2012 9:40 AM