Installing Wall-Mounted Wired
Sensors
Reference the wall-mounted zone sensor dimensions in
Figure 16, p. 46. Position the sensor on an inside wall three
to five feet above the floor and at least 18 inches from the
nearest outside wall. Installing the sensor at a lower height
may give the advantage of monitoring the temperature
closer to the zone, but it also exposes the sensor to airflow
obstructions. Ensure that air flows freely over the sensor.
Sensor
When selecting a sensor location, avoid the following:
• Areas of direct sunlight
• Areas in the direct airstream of air diffusers
• Exterior walls and other walls that have a
temperature
differential between the two sides
• Areas that are close to heat sources
such as sunlight,
appliances, concealed pipes, chimneys, or other heat-
generating equipment
• Drafty areas
• Dead spots behind doors, projection screens, or
corner
s
• Walls that are subject to high vibration
• Areas with high humidity
• High traffic areas (to reduce acci
dental damage or
tampering)
Wall-mounted wired display sensor
with setpoint adjustment:
Digit 30 = F, G, or J and Digit 31 = 4
Wall-mounted wireless temperature sensor (WZS)
(setpoint adjustment, no fan speed adjustment) and
unit-mounted receiver:
Digit 30 = F, G, or J and Digit 31 = 6
Wall-mounted wireless display sensor (WDS) and
unit-mounted receiver:
Digit 30 = F, G, or J and Digit 31 = 7
X13790886-04 (wall)
X13790821-01 (wall)
X13790860-02 (unit)
X13790822-04 (wall)
X13790860-02 (unit)
Figure 16. Wall-mounted wired and wireless zone
sensor dimensions
1. 0.31 in
2. TYP R.07 in (R1.9)
3. TYP 0.24 in)
4. 2.9 in
5. 1.08 in
6. 0.12 in
7. 3.39 in
8. 4.68 in
9. 2.48 in
10. 0.63 in
11. 1.45 in
12. 2.62 in