Installation and Maintenance Manual

Diagnostics
128 UNT-SVX07D-EN
Verify that the voltage jumper on the motor plug
harness is absent for 208-230V units and 277V units. If
the jumper is present for these units, the motor
electronics will be damaged, and the motor will not be
controllable.
Verify that the fan speed request is not below 450 rpm.
Spe
eds below 450 rpm are not supported on the fan-
coil product.
Verify that the all binary inputs
to the customer
terminal blocks are of proper and consistent polarity.
For CSTI units, the fan inputs and end device inputs
on
TB3 must receive signals that are 24 Vac with
respect to the unit chassis.
Note: Do not short 24 Vac (pos 1 or pos 2) to
chassis; refer to the unit schematic.
For Fan Speed Switch units, that incorporate the
Tracer ZN/CSTI adapter board, all inputs to TB3
must be 24 Vac with respect to unit chassis.
Note: Do not short 24 Vac (pos 1 or pos 2) to
chassis; refer to the unit schematic.
For Tracer ZN units, where there is a desire to use
parallel fan inputs on the adapter board TB3 strip,
the inputs must be COM (i.e., the inputs will honor
only 0 V with respect to unit chassis).
Note: Do not short 24 Vac (pos 1 or pos 2) to
chassis; refer to the unit schematic.
Verify that variable speed (VS
P) inputs are properly
wired to 1TB4.
Notes:
Do not
short the courtesy 10 Vdc supply to chassis
or loads that require greater than 10 mA of DC
current.
Please observe proper polarity of 0–10 Vdc inputs.
Failure to observe proper polarity can cause failure
of the ECM Engine board, the customer-supplied
controller or the Tracer ZN controller.
Verify that the signal on the
VSP inputs is noise free.
The ECM engine board contains an adjustable noise
floor parameter,
, that can be configured to reject
signals below the noise floor.
Note: If the
customer supplied controller outputs
signals that are below the noise threshold, they
will be ignored by the ECM engine.
Verify that VSP input settings are
correct. The ECM
engine board contains an adjustable digital amplifier,
, to compensate for long 10 Vdc cable runs. For
normalized (0–10 Vdc) signals, this setting should be
set to 1
.000. If it is set too high, the motors will faster
than the requested ratio, and will hit the limit

before the input voltage has reached its upper limit.
Verify that
 and , the low motor signal
output limits, are set correctly.
UNT-SVX07_-EN.book Page 128 Friday, April 27, 2012 9:40 AM