Installation and Maintenance Manual
12 UNT-SVX07D-EN
Dimensions and Weights
Table 1. Fan-coil component data
Unit Size 02 03 04 06 08 10 12
Coil Data
Face Area — ft
2
0.8 0.8 1.1 1.6 2.1 3.2 3.2
LxDxH — in.
2-Row 15 x 1.7 x 8 15 x 1.7 x 8 20 x 1.7 x 8 29.5 x 1.7 x 8 38 x 1.7 x 8 57 x 1.7 x 8 57 x 1.7 x 8
3-Row 15 x 2.6 x 8 15 x 2.6 x 8 20 x 2.6 x 8 29.5 x 2.6 x 8 38 x 2.6 x 8 57 x 2.6 x 8 57 x 2.6 x 8
4-Row 15 x 3.5 x 8 15 x 3.5 x 8 20 x 3.5 x 8 29.5 x 3.5 x 8 38 x 3.5 x 8 57 x 3.5 x 8 57 x 3.5 x 8
Volume — gal
1-Row (Heat) 0.06 0.06 0.08 0.11 0.14 0.21 0.21
2-Row 0.12 0.12 0.15 0.22 0.28 0.42 0.42
3-Row 0.18 0.18 0.23 0.33 0.42 0.62 0.62
4-Row 0.24 0.24 0.30 0.44 0.56 0.83 0.83
Fins/ft
2-Row 144 144 144 144 144 144 144
3-Row 144 144 144 144 144 144 144
4-Row 144 144 144 144 144 144 144
Reheat Coil Data (1-Row), Standard or High-Capacity
(a)
(a) Standard and high-capacity reheat coils share the same component data except that standard capacity reheat coils have 48 fins/ft (1.6 fins/cm) while
high-capacity reheat coils have 144 fins/ft (4.7 fins/cm).
Hot Water or Steam
Face Area — ft
2
0.6 0.6 0.8 1.2 1.6 2.4 2.4
L x D x H — in. 15 x 1.5 x 6 15 x 1.5 x 6 20 x 1.5 x 6 29.5 x 1.5 x 6 38 x 1.5 x 6 57 x 1.5 x 6 57 x 1.5 x 6
Volume — gal 0.12 0.12 0.15 0.22 0.28 0.42 0.42
Standard Capacity
(a)
Fins/ft 48 48 48 48 48 48 48
High-Capacity
(a)
Fins/ft 144 144 144 144 144 144 144
Fan/Motor Data
Fan Quantity 1112233
Size — Dia” x Width” 6.31 x 4 6.31 x 6.5 6.31 x 7.5 6.31 x 6.5 6.31 x 7.5 (1) 6.31 x 7.5 6.31 x 7.5
Size — Dia” x Width” (2) 6.31 x 6.5
Motor Quantity 1111122
Filter Data
1” TA and Pl. Media
Quantity 1111111
Size — in. 8-7/8 x 19-1/8 8-7/8 x 19-1/8 8-7/8 x 24-1/8 8-7/8 x 33-5/8 8-7/8 x 42-1/8 8-7/8 x 61-1/8 8-7/8 x 61-1/8
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1111111
Size — in 5-1/2 x 19-1/8 5-1/2 x 19-1/8 5-1/2 x 24-1/8 5-1/2 x 33-5/8 5-/2 x 42-1/8 5-1/2 x 61-1/8 5-1/2 x 61-1/8
UNT-SVX07_-EN.book Page 12 Friday, April 27, 2012 9:40 AM