Installation and Maintenance Manual

Maintenance
UNT-SVX07D-EN 111
Monthly Maintenance
1. Inspect unit air filters. Clean or replace if airflow is
blocked or if filters are dirty.
2. Check the main and auxiliary drain pans on fan-coil
units to be sure the pans are clean and do not impede
the condensate flow through the drain line.
Annual Maintenance
Check and tighten all set screws, bolts, locking collars and
sheaves.
1. Inspect the unit cabinetry for chips or corrosion. Clean
or repair to provide unit protection.
2. Inspect the fan wheel and ho
using for damage. Rotate
the fan wheel manually to be sure movement is not
blocked by obstructions.
3. Inspect the coil fins for excessive dirt or damage.
R
emove dirt and straighten fins.
4. Clean and tighten all electrical connections.
5. Inspect the strainer option fo
r debris trapped in the
filter screen.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturers
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
For additional information regarding the safe discharge of
capacitors, see PROD-SVB06A-EN