Installation and Maintenance Manual
Pre-Installation
UNT-SVX07D-EN 11
is continuously pitched 1 inch per 10 feet of condensate
line run to adequately drain condensate.
5. Wall & ceiling openings: Vertical recessed/concealed
u
nits require wall/ceiling openings. Refer to submittal
for specific dimensions before attempting to install.
Horizontal recessed/concealed units must meet the
requirements of the National Fire Protection
Association (NFPA) Standard 90A or 90B concerning
the use of concealed ceiling spaces as return air
plenums. Refer to the submittal for specific
dimensions of ceiling openings.
6. Exterior: Touch up painted panels if necessary. If
pa
nels need paint, sanding is not necessary. However,
clean the surface of any oil, grease, or dirt residue so
the paint will adhere. Purchase factory approved touch
up epoxy paint from your local Trane Service Parts
Center and apply.
Service Access
Service access is available from the front on vertical units
and from the bottom on horizontal units. Cabinet and
recessed units have removable front or bottom panels to
allow access into the unit. See Figure 2, p. 11 for
recommended service and operating clearances.
Units have either right or left hand piping. Reference
piping locations by facing the front of the unit (airflow
discharges from the front). The control panel is always on
the end opposite the piping.
The fan board assembly and main drain pan are easily
removable for cleaning. See “Maintenance,” p. 106 for
more details on servicing.
Pre-Installation Checklist
Complete the following checklist before beginning unit
installation.
Figure 2. Recommended service clearances
model B, vertical cabinet
model L, low vertical cabinet
12"
both sides
24"
3"
36"
model A, vertical concealed
model K, low vertical concealed
model H, vertical recessed
8.5"
both sides
12"
both sides
8.5"
both sides
28"
28"
model D, horizontal cabinet
model C, horizontal concealed
model E, horizontal recessed
24"
front discharge
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and
sufficient to support the unit and accessory weights.
See “Dimensions and Weights,” p. 12. Level or repair
the floor before positioning the unit if necessary.
Allow minimum recommended clearances for routine
maintenance and service. Refer to unit submittals for
dimensions.
Allow one and one half fan diameters above the unit
before the discharge ductwork makes any turns.
UNT-SVX07_-EN.book Page 11 Friday, April 27, 2012 9:40 AM