Performance Data
Force-Flo cabinet heater performance data is grouped based on performance. Unit performance
is impacted by the unit model and the airflow inlet and outlet configuration. Tab l e 5 summarizes
the performance groups.
Table 5. Force-Flo performance groupings
UNIT TYPE Motor Type Filter Static Performance Tables
Horizontal Concealed Free Discharge NO 0.05 Table 7 & Table 8
Horizontal Recessed Free Discharge NO 0.05
Vertical Recessed Free Discharge NO 0.05
Inverted Vertical Recessed Free Discharge NO 0.05
Vertical Concealed Free Discharge NO 0.05 Table 9 & Table 10
Horizontal Cabinet Free Discharge YES 0.00 Table 11 & Table 12
Vertical Cabinet Free Discharge YES 0.00
Inverted Vertical Cabinet Free Discharge YES 0.00
Vertical Slope Top Free Discharge YES 0.00 Table 13 & Table 14
Horizontal Concealed High Static NO 0.20 Table 15 & Table 16
Horizontal Recessed High Static NO 0.20
Vertical Recessed High Static NO 0.20
Horizontal Cabinet High Static NO 0.20
Vertical Concealed High Static NO 0.20 Table 17 & Table 18
Table 6. Steam properties
Steam Pressure (psig) 2 5 10 15
Saturated Temperature (°F) 219 227 239 250
Latent Heat (Btu/lb) 965 960 952 945
Note: Q/ITD = MBh / (saturated steam temp - entering air temp) When Δ T and gpm remain
constant. To determine heating capacities at a different saturated steam or entering air
temperature, compute the new ITD and multiply it by the new Q/ITD shown.