Catalogue

38 UNT-PRC001-EN
Performance Data
Vertical Concealed
The following performance data represents the 1-row hot water and steam reheat coils that are
available on fan-coil units in conjunction with a 2-, 3-, or 4-row cooling coil.
Heating performance is based on 55°F entering air temperature, 180°F entering hot water
temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
All performance measured on high speed tap, 115 V, 0.20 ESP, without filter. High static EC motor.
See Table 6, p. 25 for performance groupings.
Table 31. High Static EC motor—high static EC motor
SIZE
Main
Cooling
Coil
Airflow
(cfm)
Standard capacity hot water reheat coil High capacity hot water reheat coil
Motor
Power
(W)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
020 2-row 274 4.32 0.035 0.6 0.08 9.26 0.074 1.2 0.32 84
3-row 274 4.30 0.034 0.6 0.08 9.24 0.074 1.2 0.31 84
4-row 258 4.17 0.033 0.6 0.08 9.01 0.072 1.2 0.30 84
030 2-row 341 4.85 0.039 0.7 0.10 10.12 0.081 1.4 0.37 91
3-row 319 4.66 0.037 0.6 0.10 9.83 0.079 1.3 0.35 91
4-row 299 4.50 0.036 0.6 0.09 9.56 0.076 1.3 0.33 91
040 2-row 377 6.09 0.049 0.8 0.18 13.04 0.104 1.7 0.68 110
3-row 455 6.62 0.053 0.9 0.21 13.90 0.111 1.9 0.76 110
4-row 429 6.38 0.051 0.9 0.19 13.52 0.108 1.8 0.73 110
060 2-row 632 9.99 0.080 1.3 0.55 21.12 0.169 2.8 2.07 162
3-row 733 10.72 0.086 1.4 0.62 22.29 0.178 3.0 2.28 162
4-row 687 10.23 0.082 1.4 0.57 21.51 0.172 2.9 2.14 162
080 2-row 865 13.22 0.106 1.8 1.09 27.95 0.224 3.7 4.09 298
3-row 845 12.82 0.103 1.7 1.03 27.28 0.218 3.6 3.92 298
4-row 800 12.48 0.100 1.7 0.98 26.73 0.214 3.6 3.78 298
100 2-row 1089 18.64 0.149 2.5 2.74 40.20 0.322 5.4 10.76 252
3-row 1206 19.36 0.155 2.6 2.93 41.42 0.331 5.5 11.35 252
4-row 1145 18.58 0.149 2.5 2.73 40.11 0.321 5.3 10.72 252
120 2-row 1218 19.73 0.158 2.6 3.03 42.03 0.336 5.6 11.65 314
3-row 1291 20.02 0.160 2.7 3.11 42.50 0.340 5.7 11.88 314
4-row 1223 19.18 0.153 2.6 2.88 41.10 0.329 5.5 11.19 314
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Table 32. Steam coil performance—high static EC motor
SIZE
Main Cooling
Coil Airflow (cfm)
2 PSIG 5 PSIG
Motor
Power (W)
Total Capacity
(MBh) Q/ITD Heating LAT (F)
Total Capacity
(MBh) Q/ITD
Heating LAT
(F)
020 2-row 274 8.32 0.056 84.71 8.76 0.056 86.28 84
3-row 274 8.29 0.056 84.80 8.72 0.056 86.37 84
4-row 258 8.03 0.054 85.55 8.45 0.054 87.17 84
030 2-row 341 9.30 0.062 82.16 9.79 0.062 83.60 91
3-row 319 8.96 0.060 83.00 9.43 0.060 84.48 91
4-row 299 8.65 0.058 83.79 9.11 0.058 85.31 91
040 2-row 377 11.32 0.076 84.21 11.92 0.076 85.76 110
3-row 455 12.27 0.082 82.39 12.92 0.082 83.84 110
4-row 429 11.84 0.079 83.18 12.47 0.079 84.67 110
060 2-row 632 17.92 0.120 82.59 18.87 0.120 84.05 162
3-row 733 19.18 0.129 81.10 20.20 0.129 82.49 162
4-row 687 18.34 0.123 82.08 19.31 0.123 83.52 162
080 2-row 865 23.32 0.157 82.33 24.56 0.156 83.78 298
3-row 845 22.64 0.152 83.00 23.84 0.152 84.49 298
4-row 800 22.07 0.148 83.58 23.24 0.148 85.10 298
100 2-row 1089 32.29 0.217 84.04 34.02 0.217 85.60 252
3-row 1206 33.49 0.225 83.19 35.29 0.225 84.71 252
4-row 1145 32.21 0.216 84.10 33.93 0.216 85.66 252
120 2-row 1218 34.10 0.229 82.78 35.93 0.229 84.28 314
3-row 1291 34.57 0.232 82.47 36.43 0.232 83.95 314
4-row 1223 33.18 0.223 83.41 34.96 0.223 84.93 314
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Reheat Coils
UNT-PRC001-EN.book Page 38 Tuesday, May 8, 2012 10:54 AM