Catalogue
36 UNT-PRC001-EN
Performance Data
Vertical Slope Top Cabinet
The following performance data represents the 1-row hot water and steam reheat coils that are
available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil.
Heating performance is based on 55°F entering air temperature, 180°F entering hot water
temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
All performance measured on high speed tap, 115 V, zero ESP, with throwaway filter. Free discharge
EC motor. See Table 6, p. 25 for performance groupings.
Table 27. Standard Capacity and High capacity hot water reheat coil with high static motor—free discharge EC motor
SIZE
Main
Cooling
Coil
Airflow
(cfm)
Standard capacity hot water reheat coil High capacity hot water reheat coil
Motor
Power
(W)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
020 2-row 206 3.64 0.029 0.5 0.06 8.13 0.065 1.1 0.25 37
3-row 200 3.57 0.029 0.5 0.06 8.00 0.064 1.1 0.24 37
4-row 190 3.46 0.028 0.5 0.06 7.82 0.063 1.0 0.23 37
030 2-row 262 4.12 0.033 0.6 0.08 8.94 0.072 1.2 0.30 39
3-row 260 4.10 0.033 0.6 0.08 8.90 0.071 1.2 0.29 39
4-row 242 3.94 0.032 0.5 0.07 8.64 0.069 1.2 0.28 39
040 2-row 330 5.57 0.045 0.7 0.15 12.16 0.097 1.6 0.60 58
3-row 320 5.38 0.043 0.7 0.14 11.84 0.095 1.6 0.57 58
4-row 304 5.21 0.042 0.7 0.14 11.55 0.092 1.5 0.55 58
060 2-row 512 8.76 0.070 1.2 0.44 19.08 0.153 2.5 1.73 79
3-row 508 8.65 0.069 1.2 0.43 18.88 0.151 2.5 1.69 79
4-row 483 8.31 0.066 1.1 0.40 18.30 0.146 2.4 1.60 79
080 2-row 665 11.20 0.090 1.5 0.81 24.55 0.196 3.3 3.25 122
3-row 623 10.61 0.085 1.4 0.74 23.54 0.188 3.1 3.01 122
4-row 596 10.39 0.083 1.4 0.71 23.17 0.185 3.1 2.93 122
100 2-row 856 16.02 0.128 2.1 2.10 35.73 0.286 4.8 8.71 145
3-row 873 15.93 0.127 2.1 2.08 35.57 0.285 4.7 8.65 145
4-row 839 15.33 0.123 2.0 1.94 34.54 0.276 4.6 8.20 145
120 2-row 940 16.74 0.134 2.2 2.27 36.97 0.296 4.9 9.26 160
3-row 923 16.30 0.130 2.2 2.16 36.21 0.290 4.8 8.92 160
4-row 876 15.58 0.125 2.1 2.00 34.98 0.280 4.7 8.38 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when ∆T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Table 28. Steam reheat coil with high static motor—free discharge EC motor
SIZE
Main Cooling
Coil Airflow (cfm)
2 PSIG 5 PSIG
Motor
Power (W)
Total Capacity
(MBh) Q/ITD Heating LAT (F)
Total Capacity
(MBh) Q/ITD
Heating LAT
(F)
020 2-row 206 7.06 0.047 88.78 7.44 0.047 90.56 37
3-row 200 6.93 0.047 89.28 7.29 0.046 91.10 37
4-row 190 6.73 0.045 90.04 7.09 0.045 91.89 37
030 2-row 262 7.95 0.053 85.79 8.37 0.053 87.42 39
3-row 260 7.91 0.053 85.90 8.33 0.053 87.53 39
4-row 242 7.62 0.051 86.84 8.02 0.051 88.52 39
040 2-row 330 10.39 0.070 86.29 10.94 0.070 87.94 58
3-row 320 10.04 0.067 87.12 10.57 0.067 88.82 58
4-row 304 9.74 0.065 87.90 10.25 0.065 89.64 58
060 2-row 512 15.80 0.106 85.51 16.64 0.106 87.13 79
3-row 508 15.60 0.105 85.83 16.43 0.105 87.46 79
4-row 483 15.01 0.101 86.77 15.81 0.101 88.46 79
080 2-row 665 19.89 0.133 86.05 20.94 0.133 87.70 122
3-row 623 18.89 0.127 87.34 19.89 0.127 89.05 122
4-row 596 18.53 0.124 87.82 19.51 0.124 89.46 122
100 2-row 856 27.99 0.188 87.55 29.48 0.188 89.29 145
3-row 873 27.84 0.187 87.69 29.33 0.187 89.44 145
4-row 839 26.85 0.180 88.63 28.29 0.180 90.42 145
120 2-row 940 29.17 0.196 86.51 30.73 0.196 88.19 160
3-row 923 28.44 0.191 87.14 29.96 0.191 88.86 160
4-row 876 27.26 0.183 88.23 28.72 0.183 90.00 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when ∆T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Reheat Coils