Catalogue
UNT-PRC001-EN 35
Performance Data
Horizontal Cabinet and Vertical Cabinet
The following performance data represents the 1-row hot water and steam reheat coils that are
available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil.
Heating performance is based on 55°F entering air temperature, 180°F entering hot water
temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
All performance measured on high speed tap, 115 V, zero ESP, with throwaway filter. Free discharge
EC motor. See Table 6, p. 25 for performance groupings.
Table 25. Standard Capacity and High Capacity hot water reheat coil—free discharge EC motor
SIZE
Main
Cooling
Coil
Airflow
(cfm)
Standard capacity hot water reheat coil High capacity hot water reheat coil
Motor
Power
(W)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
020 2-row 222 3.77 0.030 0.5 0.07 8.35 0.067 1.1 0.26 37
3-row 217 3.70 0.030 0.5 0.06 8.23 0.066 1.1 0.26 37
4-row 204 3.58 0.029 0.5 0.06 8.03 0.064 1.1 0.25 37
030 2-row 280 4.25 0.034 0.6 0.08 9.14 0.073 1.2 0.31 39
3-row 277 4.22 0.034 0.6 0.08 9.11 0.073 1.2 0.31 39
4-row 256 4.05 0.032 0.5 0.07 8.81 0.070 1.2 0.29 39
040 2-row 349 5.72 0.046 0.8 0.16 12.42 0.099 1.7 0.63 58
3-row 338 5.51 0.044 0.7 0.15 12.06 0.096 1.6 0.59 58
4-row 320 5.32 0.043 0.7 0.14 11.74 0.094 1.6 0.57 58
060 2-row 544 9.03 0.072 1.2 0.46 19.53 0.156 2.6 1.80 79
3-row 541 8.90 0.071 1.2 0.45 19.30 0.154 2.6 1.76 79
4-row 510 8.51 0.068 1.1 0.42 18.65 0.149 2.5 1.66 79
080 2-row 706 11.49 0.092 1.5 0.85 25.05 0.200 3.3 3.37 122
3-row 659 10.84 0.087 1.4 0.77 23.95 0.192 3.2 3.11 122
4-row 627 10.61 0.085 1.4 0.74 23.55 0.188 3.1 3.01 122
100 2-row 912 16.51 0.132 2.2 2.21 36.58 0.293 4.9 9.09 145
3-row 933 16.41 0.131 2.2 2.19 36.39 0.291 4.8 9.01 145
4-row 893 15.74 0.126 2.1 2.03 35.23 0.282 4.7 8.50 145
120 2-row 996 17.19 0.138 2.3 2.37 37.74 0.302 5.0 9.61 160
3-row 976 16.69 0.134 2.2 2.25 36.88 0.295 4.9 9.22 160
4-row 921 15.90 0.127 2.1 2.07 35.52 0.284 4.7 8.63 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when ∆T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Table 26. Steam reheat coil—free discharge EC motor
SIZE
Main Cooling
Coil Airflow (cfm)
2 PSIG 5 PSIG
Motor
Power (W)
Total Capacity
(MBh) Q/ITD Heating LAT (F)
Total Capacity
(MBh) Q/ITD
Heating
LAT (F)
020 2-row 222 7.31 0.049 87.89 7.69 0.049 89.63 37
3-row 217 7.18 0.048 88.35 7.56 0.048 90.12 37
4-row 204 6.96 0.047 89.17 7.32 0.047 90.98 37
030 2-row 280 8.18 0.055 85.10 8.61 0.055 86.69 39
3-row 277 8.14 0.055 85.23 8.57 0.055 86.83 39
4-row 256 7.81 0.052 86.23 8.22 0.052 87.88 39
040 2-row 349 10.66 0.072 85.65 11.22 0.071 87.28 58
3-row 338 10.28 0.069 86.54 10.82 0.069 88.21 58
4-row 320 9.94 0.067 87.37 10.47 0.067 89.08 58
060 2-row 544 16.26 0.109 84.83 17.12 0.109 86.41 79
3-row 541 16.03 0.108 85.17 16.88 0.108 86.77 79
4-row 510 15.36 0.103 86.20 16.18 0.103 87.85 79
080 2-row 706 20.38 0.137 85.46 21.46 0.137 87.08 122
3-row 659 19.29 0.129 86.81 20.31 0.129 88.50 122
4-row 627 18.90 0.127 87.33 19.90 0.127 89.04 122
100 2-row 912 28.80 0.193 86.83 30.34 0.193 88.53 145
3-row 933 28.62 0.192 86.98 30.15 0.192 88.69 145
4-row 893 27.52 0.185 87.99 28.99 0.185 89.75 145
120 2-row 996 29.90 0.201 85.89 31.50 0.201 87.54 160
3-row 976 29.09 0.195 86.58 30.64 0.195 88.27 160
4-row 921 27.79 0.187 87.73 29.28 0.186 89.48 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when ∆T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.