Catalogue

34 UNT-PRC001-EN
Performance Data
Vertical Concealed
The following performance data represents the 1-row hot water and steam reheat coils that are
available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil.
Heating performance is based on 55°F entering air temperature, 180°F entering hot water
temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
All performance measured on high speed tap, 115 V, 0.05 ESP, without filter. Free discharge EC
motor. See Table 6, p. 25 for performance groupings.
Table 23. Standard Capacity and High Capacity hot water reheat coil—free discharge EC motor
SIZE
Main Cooling
Coil
Airflow
(cfm)
Standard capacity hot water reheat coil High capacity hot water reheat coil
Motor
Power
(W)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
Total
Capacity
(MBh) Q/ITD
Flow
Rate
(gpm)
WPD
(ft H20)
020 2-row 211 3.69 0.030 0.5 0.06 8.20 0.066 1.1 0.25 37
3-row 205 3.61 0.029 0.5 0.06 8.07 0.065 1.1 0.25 37
4-row 192 3.48 0.028 0.5 0.06 7.85 0.063 1.1 0.24 37
030 2-row 272 4.20 0.034 0.6 0.08 9.06 0.072 1.2 0.30 39
3-row 270 4.17 0.033 0.6 0.08 9.02 0.072 1.2 0.30 39
4-row 247 3.98 0.032 0.5 0.07 8.71 0.070 1.2 0.28 39
040 2-row 340 5.65 0.045 0.8 0.16 12.30 0.098 1.6 0.61 58
3-row 328 5.44 0.044 0.7 0.15 11.94 0.096 1.6 0.58 58
4-row 309 5.24 0.042 0.7 0.14 11.61 0.093 1.6 0.55 58
060 2-row 535 8.96 0.072 1.2 0.46 19.41 0.155 2.6 1.78 79
3-row 531 8.82 0.071 1.2 0.44 19.18 0.153 2.6 1.74 79
4-row 499 8.43 0.067 1.1 0.41 18.51 0.148 2.5 1.64 79
080 2-row 697 11.43 0.091 1.5 0.84 24.95 0.200 3.3 3.34 122
3-row 646 10.76 0.086 1.4 0.76 23.80 0.190 3.2 3.07 122
4-row 612 10.51 0.084 1.4 0.72 23.37 0.187 3.1 2.97 122
100 2-row 891 16.33 0.131 2.2 2.17 36.27 0.290 4.8 8.95 145
3-row 913 16.25 0.130 2.2 2.15 36.13 0.289 4.8 8.89 145
4-row 870 15.57 0.125 2.1 1.99 34.95 0.280 4.7 8.38 145
120 2-row 980 17.06 0.136 2.3 2.34 37.52 0.300 5.0 9.51 160
3-row 958 16.56 0.132 2.2 2.22 36.66 0.293 4.9 9.12 160
4-row 899 15.75 0.126 2.1 2.04 35.26 0.282 4.7 8.51 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Table 24. Steam coil performance—free discharge EC motor
SIZE
Main Cooling
Coil Airflow (cfm)
2 PSIG 5 PSIG
Motor Power
(W)
Total
Capacity
(MBh) Q/ITD
Heating LAT
(F)
Total
Capacity
(MBh) Q/ITD
Heating LAT
(F)
020 2-row 211 7.15 0.048 88.47 7.52 0.048 90.24 37
3-row 205 7.00 0.047 89.02 7.37 0.047 90.82 37
4-row 192 6.77 0.045 89.91 7.12 0.045 91.75 37
030 2-row 272 8.09 0.054 85.38 8.52 0.054 86.98 39
3-row 270 8.04 0.054 85.51 8.47 0.054 87.12 39
4-row 247 7.70 0.052 86.59 8.10 0.052 88.26 39
040 2-row 340 10.53 0.071 85.95 11.09 0.071 87.59 58
3-row 328 10.15 0.068 86.86 10.69 0.068 88.54 58
4-row 309 9.80 0.066 87.73 10.32 0.066 89.46 58
060 2-row 535 16.14 0.108 85.01 16.99 0.108 86.60 79
3-row 531 15.91 0.107 85.35 16.75 0.107 86.96 79
4-row 499 15.22 0.102 86.43 16.03 0.102 88.10 79
080 2-row 697 20.28 0.136 85.58 21.35 0.136 87.20 122
3-row 646 19.15 0.129 87.00 20.16 0.128 88.69 122
4-row 612 18.72 0.126 87.56 19.72 0.126 89.29 122
100 2-row 891 28.50 0.191 87.09 30.02 0.191 88.81 145
3-row 913 28.37 0.190 87.21 29.88 0.190 88.93 145
4-row 870 24.24 0.183 88.25 28.70 0.183 90.03 145
120 2-row 980 29.69 0.199 86.07 31.28 0.199 87.73 160
3-row 958 28.87 0.194 86.77 30.41 0.194 88.46 160
4-row 899 27.54 0.185 87.97 29.01 0.185 89.73 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.