Catalogue

UNT-PRC001-EN 33
Performance Data
Horizontal Concealed, Compact Concealed, Horizontal Recessed and Vertical Recessed
The following performance data represents the 1-row hot water and steam reheat coils that are
available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil.
Heating performance is based on 55°F entering air temperature, 180°F entering hot water
temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
All performance measured on high speed tap, 115 V, 0.05 ESP, without filter. Free discharge EC
motor. See Table 6, p. 25 for performance groupings.
Table 21. Standard Capacity and High Capacity hot water reheat coil—free discharge EC motor
SIZE
Main
Cooling
Coil
Airflow
(cfm)
Standard capacity hot water reheat coil High capacity hot water reheat coil
Motor
Power (W)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
Total
Capacity
(MBh) Q/ITD
Flow Rate
(gpm)
WPD
(ft H20)
020 2-row 246 3.96 0.032 0.5 0.07 8.67 0.069 1.2 0.28 37
3-row 242 3.89 0.031 0.5 0.07 8.55 0.068 1.1 0.27 37
4-row 222 3.73 0.030 0.5 0.06 8.27 0.066 1.1 0.26 37
030 2-row 313 4.45 0.036 0.6 0.09 9.49 0.076 1.3 0.33 39
3-row 309 4.42 0.035 0.6 0.09 9.43 0.075 1.3 0.33 39
4-row 276 4.18 0.033 0.6 0.08 9.04 0.072 1.2 0.30 39
040 2-row 381 5.95 0.048 0.8 0.17 12.81 0.102 1.7 0.66 58
3-row 365 5.69 0.046 0.8 0.16 12.37 0.099 1.7 0.62 58
4-row 340 5.46 0.044 0.7 0.15 11.98 0.096 1.6 0.59 58
060 2-row 609 9.51 0.076 1.3 0.51 20.34 0.163 2.7 1.93 79
3-row 604 9.34 0.075 1.2 0.49 20.05 0.160 2.7 1.88 79
4-row 557 8.83 0.071 1.2 0.44 19.19 0.154 2.6 1.74 79
080 2-row 790 12.02 0.096 1.6 0.92 25.94 0.208 3.5 3.58 122
3-row 724 11.22 0.090 1.5 0.81 24.60 0.197 3.3 3.26 122
4-row 676 10.92 0.087 1.5 0.78 24.08 0.193 3.2 3.14 122
100 2-row 1015 17.34 0.139 2.3 2.41 38.00 0.304 5.1 9.73 145
3-row 1052 17.22 0.138 2.3 2.38 37.80 0.302 5.0 9.64 145
4-row 1105 16.37 0.131 2.4 2.18 36.33 0.291 4.8 8.98 160
120 2-row 988 17.97 0.144 2.4 2.57 39.07 0.313 5.2 10.22 145
3-row 1074 17.33 0.139 2.3 2.41 37.99 0.304 5.1 9.72 160
4-row 993 16.36 0.131 2.2 2.18 36.33 0.291 4.8 8.97 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Table 22. Steam coil performance—free discharge EC motor
SIZE
Main Cooling
Coil Airflow (cfm)
2 PSIG 5 PSIG
Motor
Power (W)
Total Capacity
(MBh) Q/ITD
Heating LAT
(F)
Total Capacity
(MBh) Q/ITD
Heating LAT
(F)
020 2-row 246 7.65 0.051 86.73 8.06 0.051 88.41 37
3-row 242 7.53 0.051 87.14 7.93 0.051 88.84 37
4-row 222 7.22 0.048 88.21 7.60 0.048 89.96 37
030 2-row 313 8.57 0.058 84.02 9.02 0.057 85.55 39
3-row 309 8.50 0.057 84.21 8.95 0.057 85.75 39
4-row 276 8.06 0.054 85.45 8.49 0.054 87.06 39
040 2-row 381 11.07 0.074 84.74 11.66 0.074 86.31 58
3-row 365 10.61 0.071 85.77 11.17 0.071 87.39 58
4-row 340 10.19 0.068 88.76 10.73 0.068 88.44 58
060 2-row 609 17.09 0.115 83.66 18.00 0.115 85.18 79
3-row 604 16.79 0.113 84.07 17.68 0.113 85.61 79
4-row 557 15.92 0.107 85.34 16.76 0.107 86.95 79
080 2-row 790 21.28 0.143 84.43 22.41 0.143 85.99 122
3-row 724 19.93 0.134 86.00 20.99 0.134 87.64 122
4-row 676 19.42 0.130 86.64 20.45 0.130 88.32 122
100 2-row 1015 30.15 0.202 85.69 31.77 0.202 87.33 145
3-row 1052 29.97 0.201 85.84 31.57 0.201 87.49 145
4-row 988 28.56 0.192 87.04 30.09 0.192 88.75 145
120 2-row 1105 31.19 0.209 84.86 32.86 0.209 86.46 160
3-row 1074 30.14 0.202 85.69 31.76 0.202 87.34 160
4-row 993 28.55 0.192 87.05 30.08 0.192 88.76 160
Note: Q/ITD = MBh (kW)/(Entering water temperature - Entering air temperature) when T and gpm (L/s) remain constant. To determine heating capacities
at a different entering water temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
Reheat Coils
UNT-PRC001-EN.book Page 33 Tuesday, May 8, 2012 10:54 AM