Catalogue

18 UNT-PRC001-EN
General Data
Table 1. UniTrane Fan-Coil general data
Unit Size 02 03 04 06 08 10 12
Coil Data
Face Area — ft
2
0.8 0.8 1.1 1.6 2.1 3.2 3.2
LxDxH — in.
2-Row 15 x 1.7 x 8 15 x 1.7 x 8 20 x 1.7 x 8 29.5 x 1.7 x 8 38 x 1.7 x 8 57 x 1.7 x 8 57 x 1.7 x 8
3-Row 15 x 2.6 x 8 15 x 2.6 x 8 20 x 2.6 x 8 29.5 x 2.6 x 8 38 x 2.6 x 8 57 x 2.6 x 8 57 x 2.6 x 8
4-Row 15 x 3.5 x 8 15 x 3.5 x 8 20 x 3.5 x 8 29.5 x 3.5 x 8 38 x 3.5 x 8 57 x 3.5 x 8 57 x 3.5 x 8
Volume — gal
1-Row (Heat) 0.06 0.06 0.08 0.11 0.14 0.21 0.21
2-Row 0.12 0.12 0.15 0.22 0.28 0.42 0.42
3-Row 0.180.180.230.330.420.620.62
4-Row 0.240.240.300.440.560.830.83
Fins/ft
2-Row 144 144 144 144 144 144 144
3-Row 144 144 144 144 144 144 144
4-Row 144 144 144 144 144 144 144
Reheat Coil Data (1-Row), Standard or High-Capacity
(a)
Hot Water or Steam
Face Area — ft
2
0.6 0.6 0.8 1.2 1.6 2.4 2.4
L x D x H — in. 15 x 1.5 x 6 15 x 1.5 x 6 20 x 1.5 x 6 29.5 x 1.5 x 6 38 x 1.5 x 6 57 x 1.5 x 6 57 x 1.5 x 6
Volume — gal 0.12 0.12 0.15 0.22 0.28 0.42 0.42
Standard Capacity
(a)
Fins/ft 48 48 48 48 48 48 48
High-Capacity
(a)
Fins/ft 144 144 144 144 144 144 144
Fan/Motor Data
Fan Quantity 1112233
Size — Dia” x Width” 6.31 x 4 6.31 x 6.5 6.31 x 7.5 6.31 x 6.5 6.31 x 7.5 (1) 6.31 x 7.5 6.31 x 7.5
Size — Dia” x Width (2) 6.31 x 6.5
Motor Quantity 1111122
Filter Data
1” (cm) TA and Pl. Media
Quantity 1111111
Size — in. 8-7/8 x 19-1/8 8-7/8 x 19-1/8 8-7/8 x 24-1/8 8-7/8 x 33-5/8 8-7/8 x 42-1/8 8-7/8 x 61-1/8 8-7/8 x 61-1/8
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1111111
Size — in. 5-1/2 x 19-1/8 5-1/2 x 19-1/8 5-1/2 x 24-1/8 5-1/2 x 33-5/8 5-/2 x 42-1/8 5-1/2 x 61-1/8 5-1/2 x 61-1/8
(a) Standard and high-capacity reheat coils share the same component data except that standard capacity reheat coils have 48 fins/ft while high-capacity
reheat coils have 144 fins/ft.
UNT-PRC001-EN.book Page 18 Tuesday, May 8, 2012 10:54 AM