UNT-PRC001-EN.book Page 2 Tuesday, May 8, 2012 10:54 AM Introduction It isn’t just a fan and a coil… The Trane Company has redesigned the traditional fan-coil to lead the industry in: • indoor air quality (IAQ) features • easy installation and maintenance • high quality and durability • advanced controls Smaller unit footprint. Quiet operation. Two-, three-, or four-row coils. Factory-assembled, -installed, and -tested piping package with IAQ drain pan to collect condensate.
UNT-PRC001-EN.book Page 3 Tuesday, May 8, 2012 10:54 AM Table of Contents Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 General Data . . . . . . . . . . . . . . . . . . . . . . .
UNT-PRC001-EN.book Page 4 Tuesday, May 8, 2012 10:54 AM Tracer ZN520 and UC400 Additional Features . . . . . . . . . . . . . . . . . . . . . 51 End Device Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNT-PRC001-EN.book Page 5 Tuesday, May 8, 2012 10:54 AM Features and Benefits The UniTrane fan-coil meets the standards of today’s market, as well as the anticipated needs of tomorrow’s market. The tradition that company founder Reuben Trane began in the 1930s continues with the latest generation of fan-coils from The Trane Company.
UNT-PRC001-EN.book Page 6 Tuesday, May 8, 2012 10:54 AM Features and Benefits • All wall-mounted zone sensors require only low voltage control wiring from the device to the unit control box. (No line voltage.) • The controller automatically determines the unit’s correct operating mode (heat/cool) by utilizing a proportional/integral (PI) control algorithm to maintain the space temperature at the active setpoint, allowing total comfort control.
UNT-PRC001-EN.book Page 7 Tuesday, May 8, 2012 10:54 AM Features and Benefits UNT-PRC001-EN • Filters are easily removable and changed without removing the front panel on vertical cabinet units. • Motors are easy to disconnect from the fan board, allowing easy service. • The main and auxiliary drain pans are easily removable and wipe clean with a wet cloth. • The manual output test function is an invaluable troubleshooting tool.
UNT-PRC001-EN.book Page 8 Tuesday, May 8, 2012 10:54 AM Model Number Descriptions UniTrane Fan-Coil Digit 9 — Piping System/ Placement Following is a complete description of the fan-coil model number. Each digit in the model number has a corresponding code that identifies specific unit options. A = B = C = D = E = F = G = H = J K L = = = Note: Not all options are available on all cabinet styles. Contact your local Trane sales representative for more information.
UNT-PRC001-EN.book Page 9 Tuesday, May 8, 2012 10:54 AM Model Number Descriptions Digits 21, 22, 23 — Electric Heat kW — ( ) = 208V Derate 000 = 010 = 015 = 020 = 025 = 030 = 040 = 050 = 060 = 070 = 080 = 100 = No Electric Heat 1.0 kW (0.75 kW) 1.5 kW (1.1 kW) 2.0 kW (1.5 kW) 2.5 kW (1.9 kW) 3.0 kW (2.3 kW) 4.0 kW (3.0 kW) 5.0 kW (3.8 kW) 6.0 kW (4.5 kW) 7.0 kW (5.3 kW) 8.0 kW (6.0 kW) 10.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.book Page 18 Tuesday, May 8, 2012 10:54 AM General Data Table 1. Unit Size UniTrane Fan-Coil general data 02 03 04 06 08 Coil Data Face Area — ft2 0.8 0.8 1.1 1.6 2.1 LxDxH — in. 2-Row 15 x 1.7 x 8 15 x 1.7 x 8 20 x 1.7 x 8 29.5 x 1.7 x 8 38 x 1.7 x 8 3-Row 15 x 2.6 x 8 15 x 2.6 x 8 20 x 2.6 x 8 29.5 x 2.6 x 8 38 x 2.6 x 8 4-Row 15 x 3.5 x 8 15 x 3.5 x 8 20 x 3.5 x 8 29.5 x 3.5 x 8 38 x 3.5 x 8 Volume — gal 1-Row (Heat) 0.06 0.06 0.08 0.11 0.14 2-Row 0.12 0.12 0.15 0.22 0.28 3-Row 0.
UNT-PRC001-EN.book Page 19 Tuesday, May 8, 2012 10:54 AM General Data Table 2. Low vertical fan-coil general data Unit Size Coil Data Face Area—ft2 L x D x H—in. 2-Row 3-Row Volume—gal 1-Row (Heat) 2-Row 3-Row Fins/ft 2-Row 3-Row Fan/Motor Data Fan Quantity Size—Dia” x Width” Motor Quantity Filter Data 1” TA Quantity Size—in. Table 3. 04 06 1.1 1.6 2.1 20 x 1.7 x 8 20 x 2.6 x 8 29.5 x 1.7 x 8 29.5 x 2.6 x 8 38 x 1.7 x 8 38 x 2.6 x 8 0.08 0.15 0.23 0.11 0.22 0.33 0.14 0.28 0.
UNT-PRC001-EN.book Page 20 Tuesday, May 8, 2012 10:54 AM General Data Piping Packages Factory-Installed Piping Packages UniTrane fan-coils have standard piping packages available as a factory built and installed option. Piping package options are also available for the hot water reheat coil on two-pipe units equipped with either a fan speed switch or Tracer ZN520 and UC400 controller. Factory built assures all piping packages are fully tested under water for leaks and are built within strict tolerances.
UNT-PRC001-EN.book Page 21 Tuesday, May 8, 2012 10:54 AM General Data Piping Packages The deluxe piping package also includes a strainer on the entering water pipe and unions at the coil connections along with the basic components. The strainer body is cast brass construction, with a stainless steel mesh strainer that is easily removed for cleaning. The unions are forged brass construction and close with a minimum amount of effort.
UNT-PRC001-EN.book Page 22 Tuesday, May 8, 2012 10:54 AM General Data Piping Packages Three-Way Modulating Valves These valves modulate the water flow through the coil in response to a signal. Three-way valves allow water that is directed through the coil to mix with water that is directed through the bypass line. This mixture exits through the leaving water pipe. All modulating valves are three-wire floating point equal percentage valves.
UNT-PRC001-EN.book Page 23 Tuesday, May 8, 2012 10:54 AM General Data Selecting the Correct Modulating Valve Size Modulating valves are available in any of four port sizes. The port sizes relate to a Cv of 0.6, 1.1, 2.3, 2.7, 3.3, and 3.8, which is the coefficient of flow. The coefficient of flow is defined as the volume of water flow through a control valve in the fully open position with a 1 psig differential across the valve.
UNT-PRC001-EN.book Page 24 Tuesday, May 8, 2012 10:54 AM General Data Table 4. Modulating valve selections for horizontal concealed units Unit Size Coil 02 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 03 04 06 08 10 12 Table 5. Coil 02 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 2-Row 3-Row 4-Row 04 06 08 10 12 24 1.29 1.80 1.84 1.58 1.86 2.
UNT-PRC001-EN.book Page 25 Tuesday, May 8, 2012 10:54 AM Performance Data UniTrane fan-coil performance data is submitted to AHRI with units grouped based on performance. Unit performance is impacted by the unit model and the airflow inlet and outlet configuration. Below is a table which summarizes the performance groups. Table 6. UNT-PRC001-EN Fan-Coil performance groupings UNIT TYPE Motor Type Filter External Static Performance Tables Horizontal Concealed Free Discharge NO 0.
UNT-PRC001-EN.book Page 26 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Horizontal Concealed, Compact Concealed, Horizontal Recessed, and Vertical Recessed AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.05 ESP, without filter.
UNT-PRC001-EN.book Page 27 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Vertical Concealed AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.05 ESP, without filter. Free discharge EC motor. See Table 6, p. 25 for performance groupings. Table 9.
UNT-PRC001-EN.book Page 28 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Horizontal Cabinet and Vertical Cabinet AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, zero ESP, with throwaway filter. Free discharge EC motor. See Table 6, p.
UNT-PRC001-EN.book Page 29 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Vertical Slope Top Cabinet AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, zero ESP, with throwaway filter. Free discharge EC motor. See Table 6, p. 25 for performance groupings.
UNT-PRC001-EN.book Page 30 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Low Vertical Cabinet and Low Vertical Concealed AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, zero ESP, with throwaway filter. Free discharge EC motor. See Table 6, p.
UNT-PRC001-EN.book Page 31 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Horizontal Concealed, Compact Concealed, Horizontal Cabinet, Horizontal Recessed and Vertical Recessed AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.20 ESP, without filter.
UNT-PRC001-EN.book Page 32 Tuesday, May 8, 2012 10:54 AM Performance Data Main Coil Vertical Concealed AHRI cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temperature, 180°F entering hot water temperature with a 30°F ΔT. All performance measured on high speed tap, 115 V, 0.20 ESP, without filter. High static EC motor. See Table 6, p. 25 for performance groupings. Table 19.
UNT-PRC001-EN.book Page 33 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Horizontal Concealed, Compact Concealed, Horizontal Recessed and Vertical Recessed The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil.
UNT-PRC001-EN.book Page 34 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Vertical Concealed The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil. Heating performance is based on 55°F entering air temperature, 180°F entering hot water temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
UNT-PRC001-EN.book Page 35 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Horizontal Cabinet and Vertical Cabinet The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil. Heating performance is based on 55°F entering air temperature, 180°F entering hot water temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
UNT-PRC001-EN.book Page 36 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Vertical Slope Top Cabinet The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2, 3, or 4-row cooling coil. Heating performance is based on 55°F entering air temperature, 180°F entering hot water temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
UNT-PRC001-EN.book Page 37 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Horizontal Concealed, Compact Concealed, Horizontal Cabinet, Horizontal Recessed, and Vertical Recessed The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2-, 3-, or 4-row cooling coil.
UNT-PRC001-EN.book Page 38 Tuesday, May 8, 2012 10:54 AM Performance Data Reheat Coils Vertical Concealed The following performance data represents the 1-row hot water and steam reheat coils that are available on fan-coil units in conjunction with a 2-, 3-, or 4-row cooling coil. Heating performance is based on 55°F entering air temperature, 180°F entering hot water temperature (hot water coil) or 2 psig and 5 psig entering steam pressure (steam coil) and a 15°F ΔT.
UNT-PRC001-EN.book Page 39 Tuesday, May 8, 2012 10:54 AM Controls ECM Engine Controller The Electronically Commutated Motor (ECM) engine controls and reports the performance of up to two Trane Brushless DC (BLDC) motors. Figure 2. ECM engine controller • The engine also coordinates the operation of the fan in response to electric heat behavior and electric behavior in response to hydronic heat behavior.
UNT-PRC001-EN.book Page 40 Tuesday, May 8, 2012 10:54 AM Controls Control Options UniTrane fan-coils are available with four different control options: • Manual three-speed fan switch • Tracer ZN010 • Tracer ZN510 • Tracer ZN520 • Tracer UC400 Manual Fan Mode Switch Model Number Digit 30 = A and Digit 31 = D or K Figure 4. Fan speed switch Figure 5.
UNT-PRC001-EN.book Page 41 Tuesday, May 8, 2012 10:54 AM Controls The adapter allows direct customer interfacing through the use of terminal strips.
UNT-PRC001-EN.book Page 42 Tuesday, May 8, 2012 10:54 AM Controls Figure 7. 3 2 CSTI adapter board field connections 1 13 12 11 10 9 8 7 6 5 4 3 2 1 1. VSP 10V 2. VSP 0–10V 3. VSP DC COM 1. 24 Vac Y (hot) 2. 24 Vac Y (gnd) 3. High 4. Medium 5. Low 6. V1Op/Cooling 7. V1C1 (not std) 8. Not used 9. Not used 10. V2Op/EH1St/Heating 11. V2C1/EH2St (not std) 12. Damper Open 13.
UNT-PRC001-EN.book Page 43 Tuesday, May 8, 2012 10:54 AM Controls Tracer ZN510, Model Number Digit 30 = F Figure 9. Tracer ZN510 control board ZN510 can be used as either a stand-alone or communicating microprocessor controller. Tracer ZN520, Model Number Digit 30 = G The ZN520 controller can be used in a stand-alone application or as part of a Trane Integrated Comfort™ System (ICS).
UNT-PRC001-EN.book Page 44 Tuesday, May 8, 2012 10:54 AM Controls Sequence of Operation In the stand-alone configuration, UC400 receives operation commands from the zone sensor and/ or the auto changeover sensor (on auto changeover units). The entering water temperature is read from the auto changeover sensor and determines if the unit is capable of cooling or heating.
UNT-PRC001-EN.book Page 45 Tuesday, May 8, 2012 10:54 AM Controls Sequence of Operation local (hard wired), communicated, or stored default values (configurable using the Tracer TU service tool). Unoccupied Mode In unoccupied mode, the UC400 controller attempts to maintain the space temperature based on the unoccupied heating or cooling setpoint. The fan will cycle between high speed and OFF. In addition, the outdoor air damper remains closed, unless economizing.
UNT-PRC001-EN.book Page 46 Tuesday, May 8, 2012 10:54 AM Controls Sequence of Operation calculating the required heating or cooling capacity (0–100%) according to the measured zone temperature and the active zone temperature setpoint. The active zone temperature setpoint is determined by the current operating modes, which include occupancy and heat/cool modes. • Discharge air temperature control— is the backup mode that runs only if there is not valid zone temperature.
UNT-PRC001-EN.book Page 47 Tuesday, May 8, 2012 10:54 AM Controls Zone Sensor Options Zone Sensor Options Zone sensors are available as either unit, wall, or split-mounted options for design flexibility. Fancoils with the unit-mounted zone sensor option include a thermistor in the unit’s return air path. Wall-mounted zone sensor options have an internal thermistor. Zone sensors operate on 24 Vac. Tracer ZN010 Options Tracer ZN510, ZN520, and UC400 Options Figure 11.
UNT-PRC001-EN.book Page 48 Tuesday, May 8, 2012 10:54 AM Controls Zone Sensor Options Tracer ZN510, ZN520, and UC400 Options (continued) Figure 18. Wall-mounted digital zone sensor with setpoint adjustment: Digit 30 = F, G, or J and Digit 31 = 4 X13790886-04 (wall) Figure 19. Wireless zone sensor (setpoint adjustment, no fan speed adjustment): Digit 30 = F, G, or J and Digit 31 = 6 X13790821-01 (wall) X13790860-02 (unit) Figure 20.
UNT-PRC001-EN.book Page 49 Tuesday, May 8, 2012 10:54 AM Controls Control Features Control Features The following control functions are standard features on units with Tracer ZN010, ZN510, ZN520, or UC400. Entering Water Temperature Sampling Function A system that uses a two-way control valve option might not sense the correct entering water temperature during long periods when the control valve is closed.
UNT-PRC001-EN.book Page 50 Tuesday, May 8, 2012 10:54 AM Controls Control Features Manual Output Test Function NA on UC400. But will have ability through TU. This feature is an invaluable tool for troubleshooting a unit. By simply pressing the controller’s test button, service personnel can manually exercise outputs in a pre-defined sequence.
UNT-PRC001-EN.book Page 51 Tuesday, May 8, 2012 10:54 AM Controls Tracer ZN520 and UC400 Additional Features Tracer ZN520 and UC400 Additional Features Automatic Fan Speed Adjustment When configured in the AUTO mode, the fan operates at the lowest speed possible (high, medium, or low) to maintain space temperature. As the cooling load decreases, the controller switches the fan to operate at the next lower speed, and the control valve modulates the unit’s cooling capacity as required.
UNT-PRC001-EN.book Page 52 Tuesday, May 8, 2012 10:54 AM Controls End Device Options End Device Options All end device options are factory-installed and -tested. Figure 21. Control valve Two-Position Control Valves, Model Number Digits 27 and 28 = A - H Two-position valve options are available with either Tracer ZN010, ZN510, ZN520 or UC400. Valves are spring-return type, sweat connections, and available as normally open or closed. The valves respond to a 24 V signal and have 1/2-inch sweat connections.
UNT-PRC001-EN.book Page 53 Tuesday, May 8, 2012 10:54 AM Controls End Device Options Figure 22. Wiring harness Two-Position Fresh Air Damper Actuator, Model Number Digit 13 = D, E, or F (Available with all control options except ZN520) Figure 23. Two-position fresh air damper actuator This damper actuator uses a 24 V signal and is factory-wired and mounted to the damper assembly. It allows zero to 50 percent fresh air.
UNT-PRC001-EN.book Page 54 Tuesday, May 8, 2012 10:54 AM Controls End Device Options This option is a three-wire floating point, spring-return damper actuator and is factory-wired and mounted to the damper assembly. When the controller enables the economizer and the unit is in occupied mode, the fresh air damper modulates between its minimum position (editable) and the full open position to maintain setpoint temperature.
UNT-PRC001-EN.book Page 55 Tuesday, May 8, 2012 10:54 AM Electrical Data Table 37. Electric heat (kW) Unit Size Unit Voltage kW kW kW 02 115 1.0 1.5 2.0 230 1.0 1.5 2.0 277 1.0 1.5 2.0 208 0.8 1.1 1.5 115 1.0 1.5 2.0 2.5 230 1.0 1.5 2.0 2.5 277 1.0 1.5 2.0 2.5 208 0.8 1.1 1.5 1.9 2.3 115 2.0 2.5 3.0 230 2.0 2.5 3.0 277 2.0 2.5 3.0 208 1.5 1.9 115 2.0 3.0 230 2.0 3.0 277 2.0 3.0 208 1.5 2.3 115 2.0 3.0 230 2.0 277 2.0 208 1.
UNT-PRC001-EN.book Page 56 Tuesday, May 8, 2012 10:54 AM Electrical Data Table 39. Free discharge and High static electrically commutated motors (ECMs) programmed to standard ECM mode 115 Volt FLA 208–230 Volt HP 2 FLA 1 2 1 277 Volt HP 2 FLA 1 2 1 HP Unit Size 1 2 1 2 3.1 0.22 1.8 0.22 1.6 0.24) 2 3 3.1 0.22 1.8 0.22 1.6 0.24 4 3.1 0.22 1.8 0.22 1.6 0.24 6 3.1 0.22 1.8 0.22 1.6 0.24 8 3.1 0.22 1.8 0.22 1.6 10 3.1 3.1 0.22 0.22 1.8 1.8 0.22 0.
UNT-PRC001-EN.book Page 57 Tuesday, May 8, 2012 10:54 AM Electrical Data Table 43. Lowboy vertical free discharge electrically commutated motors (ECMs) programmed with reduced FLA mode Unit Size FLA 115 Volt HP 3 4 6 0.5 0.8 1 0.22 0.22 0.22 H RPM M L 1090 1090 1115 770 750 760 560 560 560 Note: Actual rpm will vary with application and configuration. Table 44.
UNT-PRC001-EN.book Page 58 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Unit Weights Table 45. Operating weights, lb Low Vertical Cabinet Models Low Vertical Concealed Models Unit Size Cabinet Models Concealed Models Recessed Models 02 97 81 78 NA NA 03 97 81 78 125 109 04 125 109 88 155 139 06 155 139 128 164 147 08 164 147 139 NA NA 10 218 200 253 NA NA 12 218 200 253 NA NA Low Vertical Cabinet Models Low Vertical Concealed Models Table 46.
UNT-PRC001-EN.book Page 59 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Vertical Concealed Vertical Concealed, Model A Vertical Concealed Unit Dimensions Unit Size 200-300 400 600 800 1000-1200 No. of Fans 1 1 2 2 3 No.
UNT-PRC001-EN.book Page 60 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Vertical Cabinet Vertical Cabinet, Model B Vertical Cabinet Unit Dimensions Unit Size 200-300 400 600 800 1000-1200 No. of Fans 1 1 2 2 3 No.
UNT-PRC001-EN.book Page 61 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Horizontal Concealed Horizontal Concealed, Model C Horizontal Concealed Unit Dimensions Unit Size 200-300 400 600 800 1000-1200 No. of Fans 1 1 2 2 3 No.
UNT-PRC001-EN.book Page 62 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Horizontal Cabinet Horizontal Cabinet, Model D Horizontal Cabinet Unit Dimensions Unit Size 200-300 400 600 800 No. of Fans 1 1 2 2 1000-1200 3 No.
UNT-PRC001-EN.book Page 63 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Horizontal Recessed Horizontal Recessed, Model E Horizontal Recessed Unit Dimensions Unit Size 200-300 400 600 800 No. of Fans 1 1 2 2 3 No.
UNT-PRC001-EN.book Page 64 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Vertical Recessed Vertical Recessed, Model H Vertical Recessed Unit Dimensions Unit Size 200-300 400 600 800 No. of Fans 1 1 2 2 3 No.
UNT-PRC001-EN.book Page 65 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Vertical Slope Top Vertical Slope Top, Model J Vertical Slope Top Unit Dimensions Unit Size 200-300 400 600 800 No. of Fans 1 1 2 2 1000-1200 3 No.
UNT-PRC001-EN.book Page 66 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Low Vertical Concealed Low Vertical Concealed, Model K Low Vertical Concealed Unit Dimensions Unit Size A 300 400 600 3’-4 5/8” 4’-2 1/8” 4’-10 7/8” B 2’-2 1/4” 2’-11 3/4” 3’-8 1/4” C 2’-3 15/16” 3’-0 13/16” 3’-9 15/16” D 1’-10 5/16” 2’-7 13/16” 3’-4 5/16” E 2’-0 1/4” 2’-9 3/4” 3’-6 1/4” Notes: 1. Coil connections are always on the drain pan side and opposite the control box. 2.
UNT-PRC001-EN.book Page 67 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Low Vertical Cabinet Low Vertical Cabinet, Model L Low Vertical Cabinet Unit Dimensions Unit Size 300 400 600 A 3’-10 15/16” 4’-8 7/16” 5’-4 15/16” B 2’-2 1/4” 2’-11 3/4” 3’-8 1/4” C 11 7/16” 1’-1 5/16” 11 7/16” D 2’-0” 2’-6” 3’-6” E 2’-0 1/4” 2’-9 3/4” 3’-6 1/4” Notes: 1. Coil connections are always on the drain pan side and opposite the control box. 2. Coil connections are 5/8” O.D. sweat.
UNT-PRC001-EN.
UNT-PRC001-EN.book Page 69 Tuesday, May 8, 2012 10:54 AM Dimensions and Weights Coil Connections Coil Connections, Vertical Units 8-3/16" RHR RMS = Reheat Supply HR = Hot Water Return HS = Hot Water Supply CR = Chilled Return CS = Chilled Water Supply 5-5/16" CS 4-7/8" RHS Note: Reheat coils are only available on units with 2-pipe main coils.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.
UNT-PRC001-EN.book Page 75 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications UniTrane Fan-Coil Mechanical Specifications Performance Data Capacity: Unit capacities are certified under Industry Room Fan-Coil Air Conditioner Certification Program in accordance with AHRI Standard 440-97. Safety: All standard units are UL listed in the United States and Canada and comply with NFPA 90A requirements.
UNT-PRC001-EN.book Page 76 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Motors All motors are brushless DC (BLDC)/electronically commutated motors (ECM) factoryprogrammed and run-tested in assembled units. The motor controller is mounted in a touch-safe control box with a built-in integrated user interface and LED tachometer.
UNT-PRC001-EN.book Page 77 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Piping packages are available in either basic or deluxe configurations. The deluxe package includes unions at the coil connections and a 20-mesh strainer on the supply side with a pressure rating on the strainer of up to 400 psig. The basic package does not include either unions or the strainer. A choice of end valves are available on both the basic and deluxe piping packages.
UNT-PRC001-EN.book Page 78 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options fan/valve operation to ensure safe operation and to ensure that two modes of heat are not operating simultaneously. A transformer is supplied on any voltage unit, eliminating the need for field installation of a step-down transformer. Unit-mounted quiet magnetic relays are supplied on all voltages.
UNT-PRC001-EN.book Page 79 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Quad Grille Outlet Figure 27. Quad grille outlet Quad grilles are square multi-directional grilles that allow four different discharge directions by rotating the grilles 90°. The quad grille construction is a black plastic material (NORYL-SE 1-731) with a 15° angle on the discharge louvers. Quad grilles are recessed into the discharge panel to prevent condensation from forming on the grille exterior.
UNT-PRC001-EN.book Page 80 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options False Backs Figure 30. False back False backs increase the depth of a vertical cabinet unit and provide a cavity through which to run piping behind the fan-coil unit. False backs are also an excellent application when installing a unit beneath a window sill that extends out past the front of the unit. False backs are 18-gage steel construction and have the same paint finish as the unit.
UNT-PRC001-EN.book Page 81 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Wall boxes have a clear anodized finish and include a single core wire mesh insect screen. The frame is 10-gage extruded aluminum alloy 6063-T5 construction. Horizontal louvers have 16-gage extruded aluminum alloy 6063-T5 construction. Wall boxes ship separate for field installation. A field supplied duct or sleeve from the wall box to the unit fresh air opening is required to provide fresh air.
UNT-PRC001-EN.book Page 82 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Manual Circuit Setter Figure 35. Manual circuit setter Material Body—Forged Brass Alloy Trim—Forged Brass Alloy All Wetted Parts Brass Temperature 250°F MAX Working Pressure 300 psi Auto Circuit Setter Figure 36. Auto circuit setter Material Body—Forged Brass Flow Cartridge—Electroless Nickel and Stainless Steel Temperature 250°F MAX Working Pressure 400 psi Pressure Drop 0.5–9.0 gpm = 2 psi ΔP 10.0–12.
UNT-PRC001-EN.book Page 83 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Control Valve Figure 37. Control valve Material Body—Forged Brass Drive Shaft Stem—Chrome-Plated Brass (Modulating) Brass (2-Position) Seat—Stainless Steel (Modulating) Ball Plug—Buna N Rubber(2-Position) Plug—High Temperature Thermoplastic (Modulating) O-Ring Seals—EPDM Rubber (2-Position) Actuator—Stainless Steel Base Plate, Aluminum Cover Temperature 200°F Max. 34°F Min.
UNT-PRC001-EN.book Page 84 Tuesday, May 8, 2012 10:54 AM Mechanical Specifications Options Gland Screw—Hex Brass Valve Body—Cast Brass Union Material Nut—Forged Brass Body—Copper Tail—Copper Strainer Figure 39.
UNT-PRC001-EN.book Page 85 Tuesday, May 8, 2012 10:54 AM Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.