Installation Guide

MCQ3 Main Technical Specications
Model MCQ3
Rated Voltage
Rated Current 20A-63A 80A-125A 160A-250A 350A-500A 630A-800A
Coil Quantity Double Coils
Wiring Method Front Back
Pole 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P 2P 3P 4P
Weight (Kg) 5.5 6 6.5 6 6.5 7 6 8 10 11 14 18 25 33 42
Operating
Current
DC100V (A) 3 3 4 3 3 4 3 4 5 5 5 7 6 6 6
AC100V/110V (A) 3 3 4 3 3 4 3 4 5 5 5 7 6 6 6
AC200V/220V (A) 1.5 1.5 2 1.5 1.5 2 2.5 2.5 2.5 2.5 2.5 3.5 3 3 3
Tripping
Current
DV100V 1A 1.5A 2A
AC100V/110V 1A 1.5A 2A
AC200V/220V 0.5A 0.7A 1A
Perfor-
mance
Short-time Withstand Current 5KA 10KA 12KA 15KA
Rated Conditional Short
Circuit Current
12.5KA 25KA 30KA 37.5KA
Connecting and Breaking
Capability
AC-33B (101e Connect • 81e Break) cos=0.35 DC-33B 1.1Ie Connect • 1.1Ie Break L/R = 1ms
Switching
Time
A power
side
Control 55ms 60ms 100ms
Break 20ms 25ms 30ms
B power
side
Control 80ms 80ms 135ms
Break 20ms 20ms 30ms
Life Electrical: 2500 operations, Mechanical: 10000 operations
Operating Recycles 120 operations / hour
Auxiliary Switch
A power side 1C, B power side 1C, Switch Capacity AC100V 5A
AC200V 2.5A DC100V 0.5A
Accessories Manual Operation Handle
15