Installation Guide

Wiring Connections
Continued:
No. Function Cable Size Remarks
10 Aux. Input 1 1.0mm
2
Ground connected is active (B-)
Details see
form 3
11 Aux. Input 2 1.0mm
2
Ground connected is active (B-)
12 Aux. Input 3 1.0mm
2
Ground connected is active (B-)
13 Aux. Input 4 1.0mm
2
Ground connected is active (B-)
14 Aux. Input 5 1.0mm
2
Ground connected is active (B-)
15 GND The common port of sensor; (B-) has already connected.
16 CHARGER (D+) 1.0mm
2
Connected with charger starter’s D+ (WL) terminals.
17 MP2 1.0mm
2
(B-) has already connected. Connected with Speed sensor,
shielding line is recommended.
18 MP1 1.0mm
2
Connected with Speed sensor, shielding line is recommend-
ed.
19 S11 1.0mm
2
Connect to stepper motor. S11 and S12 are belong to one
phase to the motor while S21 and S22 are belong to the
other phase.
20 S12 1.0mm
2
21 S21 1.0mm
2
22 S22 1.0mm
2
23 RS232 RX 0.5mm
Connected to GSM module.24 RS232 TX 0.5mm
25 RS232 GND 0.5mm
26 Gens AC Voltage (U) 1.0mm
2
Connected to U-phase of generator (2A fuse is recommend-
ed).
27 Gens AC Voltage (V) 1.0mm
2
Connected to V-phase of generator (2A fuse is recommend-
ed).
28 Gens AC Voltage (W) 1.0mm
2
Connected to W-phase of generator (2A fuse is recommend-
ed).
29 Gens AC Voltage (N) 1.0mm
2
Connected to N-phase of generator (2A fuse is recommend-
ed).
NOTE: LINK interface is parameters congured interface that can be programmed by
PC using an SG72 adapter. If there is need to remotely monitor the genset, please use the
SG361 module produced by SmartGen.