Installation Guide
Fault Inspection and Troubleshooting
All our products will be strictly inspected before delivery in order to guarantee the quality of products.
Unreliability caused by users' improper installation and misuse can be checked in accordance with the following
instructions. Please contact us or the nearest dealer for help if faults are still unresolved.
1. The Main Switch has no action
A. The start-up delay has not nished. Please wait.
B. Verify whether the lines are correctly connected, especially the mains power source, the generator power
source, and load lines.
C. Check if the control lines from the ATS to the Control Box are correctly connected.
2. Indicators do not work
A. Verify whether lines are correctly connected or not, especially the mains power source, the generator power
source, and load lines.
B. Check if the setting of each control panel delay potentiometer is correct.
3. Generator does not start in case of utility outage
A. Verify whether the ATS Control Panel control switch and generator are set in the "AUTO" position.
B. Check if the control lines from ATS to the generator's Control Box are correctly connected.