Installation Guide

Operation Instructions
Automatic Mode
1. Move the control switch of the ATS Control Panel on the AUTO position, the control mode of the generator
is "AUTO".
2. When mains are on load, the indicators "Mains Available" and "Mains On Load" will light up.
3. When mains failure occurs or utility is abnormal, the generator will be controlled by the Control Box for
"Start-up Delay" automatic start.
4. When the generator has started and the voltage is normal, the "Generator Available" indicator lights up. If
the ATS automatically switches the generator on, and the "Generator On Load" indicator lights up.
5. When the utility is restored, the "Mains Available" indicator lights up. The ATS automatically transfers to the
mains side after the generator control box has sent the "Mains on Load" signal. The "Generator on Load" light
goes off and the "Mains on Load" indicator lights up.
6. When the ATS control box detects that generator voltage is normal, the "Generator Available" indicator
lights up. The ATS transfers to the generator side when the GCT time setting is set on conditions of "Generator
on Load".