Installation Guide
DKG-173 Specications
Inputs:
R-S-T: mains phase voltages
NEUT-MN: mains neutral terminal
G: generator phase voltage
NEUT-GN: generator neutral terminal
Outputs:
MCB-MAINS CONTACTOR: normally open relay output connecting the phase-R voltage to the terminal (10A @ 
250V AC)
GCB-GENERATOR CONTACTOR: normally open relay output connecting the phase-G voltage to the terminal 
(10A @ 250V AC)
REMOTE START: normally open engine start request relay output (10A @ 28V DC / 250V AC)
LED Indicators:
G: generator set voltage present
GC: generator set contactor closed
R: power supplied from mains
RST: mains voltage present
MC: mains contactor closed
Technical Specications:
Alternator voltage:
 170-300V AC (Ph-N)
Mains Voltage:
 170-300V AC (Ph-N)
Generator contactor delay:
 1 to 40 seconds (adjustable)
Mains return delay:
 1 to 40 seconds (adjustable)
MCB relay output:
 10A @ 250V AC
GCB relay output:
 10A @ 250V AC
Remote start relay output:
 10A @ 250V AC / 28V DC
Operating temperature:
 -30 C (-22 F) to 70 C (158 F)
Storage temperature:
 -30 C (-22 F) to 80 C (176 F)
Maximum humidity:
 95% non-condensing
Dimensions:
 70 x 115 x 66mm (W x H x D)
Weight:
 180g (approx.) 
Installation:
 DIN Rail mounted
Case Material:
 High Temp. ABS/PC (UL94-V0)
IP Protection:
 IP20
Conformity (EU directives)
 -2006/95/EC (low voltage)
 -2004/108/EC (EMC)
Norms of reference:
 EN 61010 (safety requirements)
 EN 61326 (EMC requirements)
10
18-SG01D1-1A-EN