Installation Guide

Wiring Connections
Description of terminal connection: For more complete information refer to the Controller Owner’s
Manual.
No. Function Cable Size Remarks
1 B- 2.5mm
2
Connected with negative of starter battery
2 B+ 2.5mm
2
Connected with positive of starter battery. Max. 20A fuse is
recommended.
3 EM. Stop 1.5mm
2
Connected with B+ via emergency stop button
4 Fuel 1.0mm
2
Fuel relay output; B+ is supplied by 3 terminal; rated 5A
5 Crank 1.0mm
2
Start relay output; B+ is supplied by 3 terminal; rated 5A;
Connected to starter coil.
6 Aux. Output 1 1.0mm
2
B+ is supplied by 2 terminal; rated 5A
7 Aux. Output 2 1.0mm
2
B+ is supplied by 2 terminal; rated 5A;
8 Aux. Output 3 1.0mm
2
B+ is supplied by 2 terminal; rated 5A;
9 Aux. Output 4 1.0mm
2
B+ is supplied by 2 terminal; rated 5A;
24
18-SG02D1-1A-EN