Installation Guide

to stop alarm is initiated and the corresponding alarm information is displayed on LCD.
7. Now connect the red and black power leads to the circuit breaker. Since this is a single-phase application, it does
not matter which wire is connected to which lug.
8. Connect the green equipment ground wire to the ground bus bar and torque to 35 inch lbs. The torque values
are: • 10-14 AWG = 35 in/lbs. • 8 AWG = 40 in/lbs. • 4-6 AWG = 45 in/lbs.
9. Connect the white neutral wire to the neutral bus bar and torque to 35 inch lbs. The torque values are:
• 10-14 AWG = 35 in/lbs. • 8 AWG = 40 in/lbs. •4-6 AWG = 45 in/lbs.
10. IMPORTANT NOTE: Connect the control wires to the correct terminals. In order to maintain separation of
circuits, the DC control wires must be separated from the AC control wires. Wrap insulation over the AC wires OR
the DC wires, but not both, from the wire landing area to the outside of the generator. Use cable lock to hold
the insulation in place. An improperly connected control wire can damage the generator control board.
Parameter Settings
Make sure power is on before starting the controller, then press to enter into the parameters setting
menu, see g 1 below:
Fig. 1
Parameters Setting
When entering password interface, input correct password (default: 1234) can set all of the parameter items in
Form 1. If there is need to set more parameters (e.g. Voltage Calibration), please contact the factory.
CAUTION: Please change the controller parameters when generator is in standby mode only
(e. g. Crank disconnect conditions selection, auxiliary input, auxiliary output, various delay),
otherwise, shutdown and other abnormal conditions may happen.
CAUTION: Over voltage set value must be higher than under voltage set value, otherwise
over voltage and under voltage condition may occur simultaneously.
CAUTION: Over speed set value must be higher than under speed set value, otherwise over
speed and under speed condition may occur simultaneously.
CAUTION: Please set the generator frequency value as low as possible when cranking, in
order to make the starter is separated quickly as soon as possible.
1. Set Parameters
2. Information
3. Language
4. Time and Date
20