Installation Guide
Engine Prestart and Preparation
All necessary installation and maintenance must be conducted and performed by authorized licensed person-
nel.
Before starting engine for the rst time, engine oil and radiator coolant must be added. An initial uid inspec-
tion and pre-check is recommended before starting genset for the rst time or when unit has been in opera-
tion for over 20 hours. It can also be used as a quick review of all uids. Check all of the following items before
running system for the rst time.
1. Lubrication System
IMPORTANT NOTE! Unit is not shipped with engine oil or coolant from Factory!!
After installment of generator, ll engine with recommended oil weight based on ambient temperature shown
below and add radiator coolant. Prior to initial startup, replace all service panels and close lid. Start engine
and allow 10 minutes for system to warmup. After this has been performed remove service panels rise lid and
check for any leaks or drips. If found, tighten lose hoses, clamps or plugs. Recheck all uid levels and top off
as necessary.
Engine Oil. The unit is not shipped with oil from factory!!! Only use high-quality Synthetic motor detergent oil
“Classied with SAE viscosity ratings. Fill with the recommended amount of oil as specied.
Overlling or under lling can cause damage to the engine. Use the following recommended or similar
type engine oil.
Temperature
Mobil 1 Synthetic Oil or equivalent recommended
Below 32° F (0° C) SAE 0W-40
32° to 80° F (-1° to 27° C) SAE 10W-40
Above 80° F (27° C) SAE 15W-50
• Place funnel in engine oil inlet.
• First time operation will require 4 liters or (4.25qts) of oil
• Check oil gauge dipstick regularly, oil level should be kept between top and bottom lines, at all
times. It is preferred to be at the top mark but not over.
Fuel Oil Level Mark
Engine Oil
12