Installation and Maintenance Manual

Diagnostics
88 RTAE-SVX001B-EN
Operator Display Diagnostics and Messages
Comm Loss:
Winding Temp 1,
Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 1,
Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 2,
Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 2,
Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Table 34. Communication diagnostics (continued)
Diagnostic
Name
Affects
Target Severity Persistence
Active Modes
[Inactive
Modes] Criteria
Reset
Level
Table 35. Operator display diagnostics and messages
Operator Display Message
Description
//Troubleshooting
Communication Lost with UC800
Ethernet cable not connected between display and UC800.
UC800 not powered.
UC800 has an invalid configuration – Download a valid configuration
UC800 is in Binding View. When exit Binding View, select ‘Restart’ on this message
Display Failed to Establish
Communication
Ethernet cable not connected between display and UC800.
UC800 not powered.
UC800 just has the backup application running as received from the vendor. Download CTV application
software.
UC800 has an invalid configuration – Download a valid configuration
Display is about to Restart
The display is low on memory, and needs to re-start. Select Yes to restart. Selecting Yes will not affect
the UC800 operation. Only the Operator Display is reset.
File Not Found Update UC800 software with Tracer TU.
Screen partially populated. Auto and
Stop button graphics display, no text.
Valid configuration is not present. Download a configuration.
Screen Unresponsive TU is downloading software. Wait till download is complete.
The Page Cannot be found
Most likely this UC800 has only the backup application. Download the latest UC 800 software build.
This could also mean that the UC800 does not have a valid configuration. Download a configuration to it.
Cycle power to the OD and UC800.
UC could be in binding view. If so, get it out of binding view by navigating to another screen in TU.
UC800 Configuration is Invalid Update the UC800 configuration with TU.