Installation and Maintenance Manual
Diagnostics
88 RTAE-SVX001B-EN
Operator Display Diagnostics and Messages
Comm Loss:
Winding Temp 1,
Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 1,
Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 2,
Cprsr2A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Comm Loss:
Winding Temp 2,
Cprsr1A
Circuit Normal Latch All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period
Remote
Table 34. Communication diagnostics (continued)
Diagnostic
Name
Affects
Target Severity Persistence
Active Modes
[Inactive
Modes] Criteria
Reset
Level
Table 35. Operator display diagnostics and messages
Operator Display Message
Description
//Troubleshooting
Communication Lost with UC800
• Ethernet cable not connected between display and UC800.
• UC800 not powered.
• UC800 has an invalid configuration – Download a valid configuration
• UC800 is in Binding View. When exit Binding View, select ‘Restart’ on this message
Display Failed to Establish
Communication
• Ethernet cable not connected between display and UC800.
• UC800 not powered.
• UC800 just has the backup application running as received from the vendor. Download CTV application
software.
• UC800 has an invalid configuration – Download a valid configuration
Display is about to Restart
• The display is low on memory, and needs to re-start. Select Yes to restart. Selecting Yes will not affect
the UC800 operation. Only the Operator Display is reset.
File Not Found • Update UC800 software with Tracer TU.
Screen partially populated. Auto and
Stop button graphics display, no text.
• Valid configuration is not present. Download a configuration.
Screen Unresponsive • TU is downloading software. Wait till download is complete.
The Page Cannot be found
• Most likely this UC800 has only the backup application. Download the latest UC 800 software build.
• This could also mean that the UC800 does not have a valid configuration. Download a configuration to it.
• Cycle power to the OD and UC800.
• UC could be in binding view. If so, get it out of binding view by navigating to another screen in TU.
UC800 Configuration is Invalid • Update the UC800 configuration with TU.