Installation and Maintenance Manual

Controls
54 RTAE-SVX001B-EN
InvisiSound Ultimate - Noise Reduction
Mode
When the InvisiSound Ultimate option is selected (model
number digit 12=3), noise reduction mode can be enabled
to adjust fan speed and lower maximum sound levels.
Reduced acoustic noise levels can be set for certain times,
or on a schedule.The noise reduction feature can be
requested by local time of day scheduling, external input
or building automation system.
To enable this function at the external display:
Access the Settings screen on the Tracer AdaptiView.
See Figure 52.
Set the Front Panel Noise Reduction Request to ON.
Adjust the Noise Reduction Condenser Fan Speed
Clamp
to desired value.
Setting for fan speed is as a percentage of 920 rpm
maximum fan speed
Example:
For fan speed of 700 rpm, enter a value of 76%
Acceptable inputs are 60% (552 rpm) to 100% (920
rpm) in 1% increments
Figure 52. Noise reduction mode settings